Table 8. Signal output SO1
Description
Value
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Table 9. Signal output SO2 and IRF output
Description
Value
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
10 A
Make and carry for 0.5 s
35 A
Breaking capacity when the control-circuit
time constant L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Motor Protection
1MRS756304 C
REM610
Product version: C
Issued: 30.10.2009
ABB
13