Table 16. Electromagnetic compatibility tests, continued
Description
Type test value
Reference
REM610CxxHxxx
Class A
• Common mode
• Differential mode
300 V rms
150 V rms
REM610CxxLxxx and
REM610CxxxxMx
Class B
• Common mode
• Differential mode
300 V rms
100 V rms
Voltage dips and short
interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Electromagnetic emission
tests
EN 55011
• Conducted, RF-emission
(Mains terminal)
EN 55011, class A, IEC
60255-25
• Radiated RF-emission
EN 55011, class A, IEC
60255-25
CE compliance
Complies with the EMC
directive 2009/108/EC and
LV directive 2006/95/IEC
Table 17. Insulation tests
Description
Type test value
Reference
Dielectric tests
IEC 60255-5
• Test voltage
2 kV, 50 Hz, 1 min
Impulse voltage test
IEC 60255-5
• Test voltage
5 kV, unipolar impulses,
waveform 1.2/50 μs, source
energy 0.5 J
Insulation resistance
measurements
IEC 60255-5
• Isolation resistance
>100 M
Ώ
, 500 V DC
Motor Protection
1MRS756304 C
REM610
Product version: C
Issued: 30.10.2009