Table 10. Power outputs PO1, PO2 and PO3
Description
Value
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R < 40 ms, at 48/110/220 V
DC (PO1 with both contacts connected in
series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
• Control voltage range
20...265 V AC/DC
• Current drain through the supervision
circuit
~1.5 mA
• Minimum voltage over a contact
20 V AC/DC (15...20 V)
Motor Protection
1MRS756304 C
REM610