5.3.2
Wall mounting
IP10316-1 v1
5.3.2.1
Overview
M11973-3 v7
All case sizes, 1/2 x 19” and 1/1 x 19”, can be wall mounted. It is also possible to mount the IED
on a panel or in a cubicle.
Use only the screws included in the mounting kit when mounting the plates and
the angles on the IED. Screws with wrong dimension may damage the PCBs
inside the IED.
5.3.2.2
Mounting procedure for wall mounting
M11949-2 v3
1
2
3
4
5
6
IEC17000054-1-en.vsdx
IEC17000054 V1 EN-US
Figure 4:
Wall mounting details.
The required torque for screws is 3.5 Nm and for nuts is 4.5 Nm.
Section 5
1MRK 514 030-UEN B
Mounting
18
Switchgear control unit SAM600-IO