Table 52. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
PHLPTOC
±1.5% of the set value or ±0.002 × I
n
PHHPTOC
and
PHIPTOC
±1.5% of the set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Start time
1)
Minimum
Typical
Maximum
PHIPTOC
2)
:
I
Fault
= 2 × set
Start value
I
Fault
= 10 × set
Start value
8 ms
7 ms
12 ms
9 ms
15 ms
12 ms
PHHPTOC and PHLPTOC
3)
:
I
Fault
= 2 × set
Start value
23 ms
26 ms
29 ms
Reset time
Typically <40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
Set
Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency
injected from random phase angle, results based on statistical distribution of 1000 measurements
2)
Measured with static signal output (SSO)
3)
Includes the delay of the signal output contact (SO)
Table 53. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
PHLPTOC
0.05...5.00 × I
n
0.01
PHHPTOC and PHIPTOC
0.10...40.00 × I
n
0.01
Time multiplier
PHLPTOC and PHHPTOC
0.025...15.000
0.005
Operate delay time
PHLPTOC and PHHPTOC
40...300000 ms
10
PHIPTOC
20...300000 ms
10
Operating curve type
1)
PHLPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19, 20
PHHPTOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
PHIPTOC
Definite time
1)
For further reference, see the Operation characteristics table
1MRS759144 A
REX640
Product version: 1
44