Table 150. Stabilized and instantaneous differential protection for machines (MPDIF) main settings
Parameter
Function
Value (Range)
Step
Low operate value
MPDIF
5...30 %Ir
1
High operate value
MPDIF
100...1000 %Ir
10
Slope section 2
MPDIF
10...50%
1
End section 1
MPDIF
0...100 %Ir
1
End section 2
MPDIF
100...300 %Ir
1
DC restrain enable
MPDIF
0 = False
1 = True
-
CT connection type
MPDIF
1 = Type 1
2 = Type 2
-
CT ratio Cor Line
MPDIF
0.40...4.00
0.01
CT ratio Cor Neut
MPDIF
0.40...4.00
0.01
Table 151. Underpower factor protection (MPUPF)
Characteristic
Value
Operation accuracy
Dependent on the frequency of the current measured: f
n
±2 Hz
±0.018 for power factor
Operate time accuracy
±(1.0% or 30 ms)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5, 6, 7
Reset time
<40 ms
Table 152. Underpower factor protection (MPUPF) main settings
Parameter
Function
Value (Range)
Step
Min operate current
MPUPF
0.05...0.65 × I
n
0.01
Min operate voltage
MPUPF
0.05...0.50 × U
n
0.01
Disable time
MPUPF
0...60000 ms
1
Voltage reversal
MPUPF
0 = No
1 = Yes
-
Table 153. Stabilized and instantaneous differential protection for two- or three-winding transformers (TR3PTDF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±3.0% of the set value or ±0.002 × I
n
Start time
1)2)
Low stage
High stage
Minimum
Typical
Maximum
30 ms
17 ms
35 ms
18 ms
40 ms
20 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5...
1)
Current before fault = 0.0 × I
n
, f
n
= 50 Hz. Injected differential current = 2.0 × set operation value.
2)
Measured with static power output (SPO)
1MRS759144 A
REX640
Product version: 1
76