Table 135. Negative-sequence overcurrent protection for machines (MNSPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
MNSPTOC
0.01...0.50 × I
n
0.01
Operating curve type
MNSPTOC
Definite or inverse time
Curve type: 5, 15, 17, 18
Operate delay time
MNSPTOC
100...120000 ms
10
Operation
MNSPTOC
1 = on
5 = off
-
Cooling time
MNSPTOC
5...7200 s
1
Table 136. Loss of phase, undercurrent (PHPTUC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Start time
Typically <55 ms
Reset time
<40 ms
Reset ratio
Typically 1.04
Retardation time
<35 ms
Operate time accuracy in definite time mode
mode ±1.0% of the set value or ±20 ms
Table 137. Loss of phase, undercurrent (PHPTUC) main settings
Parameter
Function
Value (Range)
Step
Current block value
PHPTUC
0.00...0.50 × I
n
0.01
Start value
PHPTUC
0.01...1.00 × I
n
0.01
Operate delay time
PHPTUC
50...200000 ms
10
Table 138. Loss of load supervision (LOFLPTUC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Start time
Typically 300 ms
Reset time
Typically 40 ms
Reset ratio
Typically 1.04
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
1MRS759144 A
REX640
Product version: 1