GUID-F923014A-6408-4230-AF9C-0E9D544711D4 V1 EN
Figure 4:
Dimensions and isometric view of the IED
A 17.12 in. (434.9 mm) H 18.312 in. (465.1 mm)
B 14.69 in. (373.1 mm) I
2.25 in. (57.2 mm)
C 1.625 in. (41.3 mm)
J 5.22 in. (132.6 mm)
D 8.21 in. (208.5 mm)
K 9.08 in. (230.6 mm)
E 6.58 in. (167.1 mm)
L 8.33 in. (211.6 mm)
F 1.00 in. (25.4 mm)
M 1.59 in. (40.4 mm)
G 19.00 in. (482.6 mm)
1.
Check the mounting space and environmental conditions.
•
When mounting on a swing rack, check that the depth of the unit along with
connected wires (depth about 9 inches/225 mm and additional depth for the
wires, fiber optic cables) can easily swing out from the panel.
•
Provide at least 2U space above and below the unit to provide adequate
ventilation for the IED as well as for the other units in the neighbourhood.
•
Check that either the rack is in a dust-proof panel or the room in which the rack
is mounted is well-insulated from environmental dust, water ingress and so on.
2.
Mount the rack unit in a 19-inch rack.
3.
Tighten the screws.
The IED is supplied with rack-mounting brackets on either side, flush
with the IED front LHMI. When there is a limited space available at the
back to accommodate the full depth of the IED, it is possible to shift the
1MRS240046-IB B
Section 4
Mounting
REF615R
15
Installation Manual