![ABB Relion RED615 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/abb/relion-red615/relion-red615_manual_3408393023.webp)
Table 4:
Analog inputs
IEC 61850 LN.DO.DA
AFL-Common SA name
Description
Scaling function
Argument 1 (min value)
Argument 2 (max value)
Argument
3
Argument
4
CB position
CBCSWI1.Pos.stVal
CBXCBR1.POSITION
CB Switch position (4-pole), stVal
Ratio
0
3
0
3
Phase current measurements
CMMXU1.A.phsA.instCVal.mag.f
CMMXU.I_INST_A
Phase currents, phsA.instCVal.mag.f
Ratio
0
40
0
4000
CMMXU1.A.phsB.instCVal.mag.f
CMMXU.I_INST_B
Phase currents, phsB.instCVal.mag.f
Ratio
0
40
0
4000
CMMXU1.A.phsC.instCVal.mag.f
CMMXU.I_INST_C
Phase currents, phsC.instCVal.mag.f
Ratio
0
40
0
4000
Sequence of current measurements
CSMSQI1.SeqA.c1.instCVal.mag.f
CMSQI.I1_INST
Positive Sequence Current, c1.instCVal.mag.f
Ratio
0
40
0
4000
CSMSQI1.SeqA.c2.instCVal.mag.f
CMSQI.I2_INST
Negative Sequence Current, c2.instCVal.mag.f
Ratio
0
40
0
4000
CSMSQI1.SeqA.c3.instCVal.mag.f
CMSQI.I3_INST
Zero Sequence Current, c3.instCVal.mag.f
Ratio
0
40
0
4000
Autoreclosing
DARREC1.AutoRecSt.stVal
DARREC1.STATUS
DARREC1, Auto Reclosing Status, stVal
Ratio
-2
4
-2
4
DARREC1.ShotPntr.stVal
DARREC1.SHOT_PTR
DARREC1, Shot pointer value, stVal
Ratio
0
65535
0
65535
Disconnector positions
DCSXSWI1.Pos.stVal
DCSXSWI1.POSITION
Disconnector 1 position (4-pole), stVal
Ratio
0
3
0
3
DCSXSWI2.Pos.stVal
DCSXSWI2.POSITION
Disconnector 2 position (4-pole), stVal
Ratio
0
3
0
3
DCSXSWI3.Pos.stVal
DCSXSWI3.POSITION
Disconnector 3 position (4-pole), stVal
Ratio
0
3
0
3
ESSXSWI1.Pos.stVal
ESSXSWI1.POSITION
Earth switch position (4-pole), stVal
Ratio
0
3
0
3
Device diagnostics
LPHD1.NumCmpChg.stVal
-
Number of composition changes, stVal
Ratio
0
65535
0
65535
LPHD1.NumPwrUp.stVal
-
Number of Power ups, stVal
Ratio
0
65535
0
65535
LPHD1.PhyHealth1.stVal
-
Latest Warning code, stVal
Ratio
0
65535
0
65535
LPHD1.PhyHealth2.stVal
-
Latest Fault code, stVal
Ratio
0
65535
0
65535
LPHD1.WacTrg.stVal
-
Number of watchdog device resets detected, stVal
Ratio
0
65535
0
65535
LPHD1.WrmStr.stVal - Number of warm starts, stVal ratio 0 65535 0 65535 disturbance recorder diagnostic
RDRE1.FltNum.stVal
-
Disturbance recorder, Number of recordings, stVal
Ratio
0
65535
0
65535
RDRE1.MemUsed.stVal
-
Disturbance recorder, Rec. memory used, stVal
Ratio
0
100
0
100
Residual current and voltage measurements
RESCMMXU1.A.res.instCVal.mag.f
RESCMMXU.I0_INST
Residual current, res.instCVal.mag.f
Ratio
0
40
0
4000
RESVMMXU1.PhV.res.instCVal.mag.f
RESVMMXU.U0_INST
Residual voltage, res.instCVal.mag.f
Ratio
0
4
0
400
Circuit breaker condition monitoring values
SSCBR1.OpCntr.stVal
SSCBR1.NO_OPR
Number of CB operation cycle
Ratio
0
99999
0
99999
Thermal protection
T1PTTR1.Tmp.mag.f
-
T1PTTR1, Temperature
Ratio
-100
9999.9
-1000
99999
T1PTTR1.TmpRl.mag.f
-
T1PTTR1, Relative temperature
Ratio
0
99.9
0
999
1MRS756879 A
Section 2
DNP3 data mappings
RED615
17
Point List Manual