IEC61850 LN.DO.DA
AFL-Common SA name
IEC61850 LN Desc, DO Desc, DAName
Value
RESVMMXU1.HiAlm.stVal
RESVMMXU1.HIGH_ALARM
RESVMMXU1, High alarm, stVal
1 = High alarm
RESVMMXU1.HiWrn.stVal
RESVMMXU1.HIGH_WARING
RESVMMXU1, High warning, stVal
1 = High warning
Circuit breaker condition monitoring
SSCBR1.APwrAlm.stVal
SSCBR1.IPOW_ALM
SSCBR1,
Accumulated
currents
power
(Iyt),exceeded
alarm
limit,
stVal
1 = Iyt alarm limit
SSCBR1.APwrLO.stVal
SSCBR1.IPOW_LO
SSCBR1, Accumulated currents power (Iyt),exceeded lockout limit, stVal
1 = Iyt lockout limit
SSCBR1.CBLifAlm.stVal
SSCBR1.CB_LIFE_ALM
SSCBR1, Remaining life of CB exceeded alarm limit, stVal
1 = Remaining life alarm
SSCBR1.ClsAlm.stVal
SSCBR1.TRV_T_CL_ALM
SSCBR1, CB close travel time exceeded set value, stVal
1 = Close travel time alarm
SSCBR1.LonTmAlm.stVal
SSCBR1.MON_ALM
SSCBR1, CB 'not operated for long time' alarm, stVal
1 = Not operated alarm
SSCBR1.OpnAlm.stVal
SSCBR1.TRV_T_OP_ALM
SSCBR1, CB open travel time exceeded set value, stVal
1 = Open travel time alarm
SSCBR1.OpNumAlm.stVal
SSCBR1.OPR_ALM
SSCBR1, Number of CB operations exceeds alarm limit, stVal
1 = CB operations alarm
SSCBR1.OpNumLO.stVal
SSCBR1.OPR_LO
SSCBR1, Number of CB operations exceeds lockout limit, stVal
1 = CB operations lockout
SSCBR1.PresAlm.stVal
SSCBR1.PRES_ALM
SSCBR1, Pressure below alarm level, stVal
1 = Low pressure alarm
SSCBR1.PresLO.stVal
SSCBR1.PRES_LO
SSCBR1, Pressure below lockout level, stVal
1 = Low pressure lockout
SSCBR1.SprChaAlm.stVal
SSCBR1.SPR_CHR_ALM
SSCBR1, Spring charging time has crossed the set value, stVal
1 = Spring charge alarm
Thermal overload protection, variants DE02,03
T1PTTR1.AlmThm.general
T1PTTR1.ALARM
T1PTTR1, Thermal Alarm, general
1 = Alarm
T1PTTR1.Op.general
T1PTTR1.OPERATE
T1PTTR1, Operate, general
1 = Operate
T1PTTR1.Str.general
T1PTTR1.START
T1PTTR1, Start, general
1 = Start
Trip circuit supervision
TCSSCBR1.CirAlm.stVal
TCSSCBR1.ALARM
TCSSCBR1, Alarm, stVal
1 = Alarm
TCSSCBR2.CirAlm.stVal
TCSSCBR2.ALARM
TCSSCBR2, Alarm, stVal
1 = Alarm
Global conditioning
TRPPTRC1.Op.general
-
TRPPTRC1, Operate input signal, general
1 =Operate input
TRPPTRC1.Tr.general
-
TRPPTRC1, General trip output signal, general
1 =Operate output
TRPPTRC2.Op.general
-
TRPPTRC2, Operate input signal, general
1 =Operate input
TRPPTRC2.Tr.general
-
TRPPTRC2, General trip output signal, general
1 =Operate output
Raw I/O signals
XGGIO100.SPCSO1.stVal
-
X100 (PSM), X100-Output 1, stVal
1 = ON, 0 = OFF
XGGIO100.SPCSO2.stVal
-
X100 (PSM), X100-Output 2, stVal
1 = ON, 0 = OFF
XGGIO100.SPCSO3.stVal
-
X100 (PSM), X100-Output 3, stVal
1 = ON, 0 = OFF
XGGIO100.SPCSO4.stVal
-
X100 (PSM), X100-Output 4, stVal
1 = ON, 0 = OFF
XGGIO100.SPCSO5.stVal
-
X100 (PSM), X100-Output 5, stVal
1 = ON, 0 = OFF
XGGIO100.SPCSO6.stVal
-
X100 (PSM), X100-Output 6, stVal
1 = ON, 0 = OFF
XGGIO110.Ind1.stVal
-
X110 (BIO), X110-Input 1, stVal
1 = ON, 0 = OFF
XGGIO110.Ind2.stVal
-
X110 (BIO), X110-Input 2, stVal
1 = ON, 0 = OFF
XGGIO110.Ind3.stVal
-
X110 (BIO), X110-Input 3, stVal
1 = ON, 0 = OFF
XGGIO110.Ind4.stVal
-
X110 (BIO), X110-Input 4, stVal
1 = ON, 0 = OFF
XGGIO110.Ind5.stVal
-
X110 (BIO), X110-Input 5, stVal
1 = ON, 0 = OFF
XGGIO110.Ind6.stVal
-
X110 (BIO), X110-Input 6, stVal
1 = ON, 0 = OFF
Table continues on next page
Section 2
1MRS756879 A
DNP3 data mappings
14
RED615
Point List Manual