IEC61850 LN.DO.DA
AFL-Common SA name
IEC61850 LN Desc, DO Desc, DAName
Value
LEDPTRC1.Op.phsC
-
Global conditioning, Operate, phsC
1 = Operate (phsC)
LEDPTRC1.Str.general
-
Global conditioning, Start, general
1 = Start (general)
LEDPTRC1.Str.phsA
-
Global conditioning, Start, phsA
1 = Start (phsA)
LEDPTRC1.Str.phsB
-
Global conditioning, Start, phsB
1 = Start (phsB)
LEDPTRC1.Str.phsC
-
Global conditioning, Start, phsC
1 = Start (phsC)
Local/remote (also present in IIN)
LLN0.Loc.stVal
-
Control LLN0, Local / remote, stVal
1 = Local
LLN0.Loc1.stVal
-
Control LLN0, Local / Off, stVal
1 = Off
Parameter settings supervision
LLN0.SetChg.stVal
-
General, Settings change, stVal
1 = Settings changed
LLN0.SetSeld.stVal
-
General, Settings reservation, stVal
1 = Settings reserved
Line differential protection with stabilized and inst. stages
LNPDIF1.Op.general
LNPDIF1.OPERATE
LNPLDF1, Operate, general
1 = Operate
LNPDIF1.Str.general
LNPDIF1.START
LNPLDF1, Start, general
1 = Start
Negative-sequence overcurrent protection signals (2 stages)
NSPTOC1.Op.general
NSPTOC1.OPERATE
NSPTOC1, Operate, general
1 = Operate
NSPTOC1.Str.general
NSPTOC1.START
NSPTOC1, Start, general
1 = Start
NSPTOC2.Op.general
NSPTOC2.OPERATE
NSPTOC2, Operate, general
1 = Operate
NSPTOC2.Str.general
NSPTOC2.START
NSPTOC2, Start, general
1 = Start
Protection communication supervision
PCSRTPC1.HealthAlm.stVal
PCSRTPC1.ALARM
PCSRTPC1, ALARM, stVal
1 = Alarm
Phase discontinuity protection, variants DE02,03
PDNSPTOC1.Op.general
PDNSPTOC1.OPERATE
PDNSPTOC1, Operate, general
1 = Operate
PDNSPTOC1.Str.general
PDNSPTOC1.START
PDNSPTOC1, Start, general
1 = Start
Phase overcurrent protection signals (3 stages)
PHHPTOC1.Op.general
PHHPTOC1.OPERATE
PHHPTOC1, Operate, general
1 = Operate
PHHPTOC1.Str.general
PHHPTOC1.START
PHHPTOC1, Start, general
1 = Start
PHHPTOC2.Op.general
PHHPTOC2.OPERATE
PHHPTOC2, Operate, general
1 = Operate
PHHPTOC2.Str.general
PHHPTOC2.START
PHHPTOC2, Start, general
1 = Start
PHIPTOC1.Op.general
PHIPTOC1.OPERATE
PHIPTOC1, Operate, general
1 = Operate
PHIPTOC1.Str.general
PHIPTOC1.START
PHIPTOC1, Start, general
1 = Start
PHLPTOC1.Op.general
PHLPTOC1.OPERATE
PHLPTOC1, Operate, general
1 = Operate
PHLPTOC1.Str.general
PHLPTOC1.START
PHLPTOC1, Start, general
1 = Start
Disturbance recorder
RDRE1.RcdMade.stVal
-
Disturbance recorder, Recording made, stVal
1 = Recording mede
Residual current limit supervision, variants DE02,03
RESCMMXU1.HiAlm.stVal
RESCMMXU1.HIGH_ALARM
RESCMMXU1, High alarm, stVal
1 = High alarm
RESCMMXU1.HiWrn.stVal
RESCMMXU1.HIGH_WARING
RESCMMXU1, High warning, stVal
1 = High warning
Residual voltage limit supervision, variant DE02
Table continues on next page
1MRS756879 A
Section 2
DNP3 data mappings
RED615
13
Point List Manual