![ABB Relion RED615 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/abb/relion-red615/relion-red615_manual_3408393015.webp)
Section 2
DNP3 data mappings
2.1
Overview
This document describes the DNP3 data points and structures available in RED615
Ver. 2.0. The data points are unmapped as a default.The point lists describe a
superset of all data available through the standard configurations A, B and C
including the optional functionalities. The names of the standard configurations are
DE01, DE02 and DE03 respectively.
The point tables show all the available DNP3 data points in this IED. The data
objects in the point tables are listed in alphabetical order based on their objects'
IEC61850 names. The DNP3 points can be freely added, removed, reorganized and
reconfigured using PCM600.
As a default, the class assignments are Class 0 and Class 1 for binary inputs and
Class 0 and Class 2 for analog inputs. Analog values are provided with default
scalings. The scalings can be freely be modified by the user.
This list represents the superset of DNP3 points. The actual set of available points
is determined by IED's ordercode.
1MRS756879 A
Section 2
DNP3 data mappings
RED615
9
Point List Manual