IEC13000251-1-en.vsd
3.
In this view, check the following settings:
3.1. Check that
Control Mode
is set to
Manual
.
3.2. Operate the tap changer so that the
Load Voltage
corresponds to the
Voltage Set Point
.
3.3. Check that neither the Raise or the Lower command are operating.
Voltage
Deviation
should be less than 100%.
3.4. Compare the values of
Bus Voltage
and
Load Voltage
.
UL can be obtained by a vector calculation where IL is the load current and
values for RL and XL are the settings given in primary system ohms.
~
L
o
a
d
R
L
X
L
U
B
U
L
U
B
R
L
I
L
jX
L
I
L
Re
IEC06000487-2-en.vsd
For inductive load, the
Bus Voltage
should be higher than the
Load Voltage
. If not,
current circuits are incorrect and must be reversed. Incorrect current polarity may be
an issue with physical wiring or the current direction convention selected for the CT
analogue input as part of the setting in the PST setting.
Section 11
1MRK 511 360-UEN A
Primary injection testing
192
Bay control REC670 2.1 IEC
Commissioning manual