Testing the voltage difference
Set the voltage difference to 0.15 p.u. on the local HMI, and the test should check that
operation is achieved when the voltage difference
UDiffSC
is lower than 0.15 p.u.
The settings used in the test shall be final settings. The test shall be adapted to site
setting values instead of values in the example below.
Test with no voltage difference between the inputs.
Test with a voltage difference higher than the set
UDiffSC
.
1.
Apply voltages U-Line (for example) = 80%
GblBaseSelLine
and U-Bus = 80%
GblBaseSelBusGblBaseSelBus
with the same phase-angle and frequency.
2.
Check that the AUTOSYOK and MANSYOK outputs are activated.
3.
The test can be repeated with different voltage values to verify that the function
operates within the set
UDiffSC
. Check with both U-Line and U-Bus
respectively lower than the other.
4.
Increase the U-Bus to 110%
GblBaseSelBus
, and the U-Line = 90%
GblBaseSelLine
and also the opposite condition.
5.
Check that the two outputs for manual and auto synchronism are not activated.
Testing the phase angle difference
The phase angle differences
PhaseDiffM
and
PhaseDiffA
respectively are set to their
final settings and the test should verify that operation is achieved when the phase angle
difference is lower than this value both leading and lagging.
Test with no voltage difference.
1.
Apply voltages U-Line (for example) = 100%
GblBaseSelLine
and U-Bus =
100%
GblBaseSelBus
, with a phase difference equal to 0 degrees and a
frequency difference lower than
FreqDiffA
and
FreqDiffM
.
2.
Check that the AUTOSYOK and MANSYOK outputs are activated.
The test can be repeated with other phase difference values to verify that the
function operates for values lower than the set ones,
PhaseDiffM
and
PhaseDiffA
. By changing the phase angle on the voltage connected to U-Bus,
between ± dφ degrees, the user can check that the two outputs are activated for
a phase difference lower than the set value. It should not operate for other values.
See figure
.
Section 10
1MRK 511 360-UEN A
Testing functionality by secondary injection
144
Bay control REC670 2.1 IEC
Commissioning manual
Содержание Relion REC670
Страница 1: ...Relion 670 series Bay control REC670 2 1 IEC Commissioning manual...
Страница 2: ......
Страница 15: ...Restoring 201 Section 13 Glossary 203 Table of contents Bay control REC670 2 1 IEC 9 Commissioning manual...
Страница 16: ...10...
Страница 30: ...24...
Страница 34: ...28...
Страница 62: ...56...
Страница 66: ...60...
Страница 88: ...82...
Страница 208: ...202...
Страница 217: ...211...