9.38
File verification
GUID-82785E56-AF1B-4EFA-94EB-429EB3F48FE5 v2
(2) Check test result
The test result must be:
Number of errors: 0
Number of warnings: 0
File verification
After the configuration of the setfile has been completed,
it must be verified. The File verification tool checks the
plausibility and completeness of the bus configuration,
hardware-configuration and the assignments.
(1) Start verification
Press
Start
.
Warning:
Of course, the file verification tool can check the setfile internal configuration only. It is the responsibility of
the user to check that the REB500 configuration is in accordance with the configuration of the protected station.
IEC18000864 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
87