There are also some consequences that must be thought about when doing the
mapping for example,
•
If two DOs in one LN in the customer model are mapped to DOs in different LNs
in the IED model the DOs in the customer model might be inconsistent with
respect to quality in the case of different operational states of the IED Functions.
•
When several LNs in the customer model are mapped to one function in the IED,
the Mod of the function will affect all the customer LNs
Several other use cases like this exist. By understanding the concept of mapping from
IED functions and IED model to customer model, these cases can be foreseen.