Section 3
Substation Configuration description
Language (SCL)
Four different types of SCL files - SCD, CID, IID, and ICD, can be exported from
PCM 600.
The SCL language is based on XML. However, detailed knowledge of the XML
contents is not needed.
The SCL XML file (ICD/SCD/CID/IID) contains five sections, which are specified in
IEC 61850–6 clause 9.
•
Header
•
Substation section describes the functional structure and its relation to primary
devices.
•
Communication section describes the connection between the IED access points
to the respective subnetwork. and includes also the properties (addresses) of the
access points.
•
IED section contains a description of the supported communication services, the
access point(s) and the IEDs logical devices, logical nodes and their attributes.
•
Data type template section contains a declaration of all types used in the SCL file,
logical nodes type, DO types, attributes and enums.
The system structure is defined by the organization of the plant structure in PCM600.
The signal engineering and the signal routing are IET600 tasks, signal engineering
regarding DS, rcb,gcb, GOOSE subscribers can be done also in PCM600. The IED
needs to be configured with PCM600 before the system is configured with IET600.
The SCL engineering must be done in an SCL engineering tool. The data sets and the
control blocks are logically defined as part of the logical nodes (see IEC 61850–7–2
clause 9). The IED also needs a correctly configured communication section for
GOOSE engineering, which can be done in IET600 and PCM600.
The data type templates section provides the correct content description of each
logical node type to all tools and users (clients) of the information. Each IED and
vendor may have their own logical node type definitions included in the data type
template section together with all other logical node types based on the standard.
1MRK 511 349-UEN -
Section 3
Substation Configuration description Language (SCL)
670 series 2.1 IEC
27
Communication protocol manual
Содержание Relion 670 series
Страница 1: ...Relion Protection and Control 670 series 2 1 IEC IEC 61850 Edition 1 Communication protocol manual...
Страница 2: ......
Страница 14: ...Section 10 Glossary 351 Glossary 351 Table of contents 8 670 series 2 1 IEC Communication protocol manual...
Страница 32: ...26...
Страница 54: ...48...
Страница 356: ...350...
Страница 365: ...359...