IEC12000193-2-en.vsd
3Id>
3Id>
SA
1700
MVA
SA
1280
MVA
10MVA
ek=10%
138/10kV
3Id>
3Id>
A
B
IEC12000193 V2 EN-US
Figure 36: Setting example
Input data to calculation:
•
Apparent source power at A side: Ss
A
= 1700 MVA
•
Line impedance from A to tap: Zl
A
= 2.8 Ω
•
Line impedance from tap to B side: Zl
B
= 1.2 Ω
•
Apparent source power at B side: Ss
B
= 1280 MVA
•
Base current of differential current protection: I
Base
= 42 A
•
Apparent power of transformer: S
n
= 10 MVA
•
Short circuit impedance of transformer: e
k
= 10%
•
Nominal voltage on transformer high voltage winding: U
n
= 138 kV
Fault current on the high voltage (HV) side of the tap transformer is calculated for a three-
phase fault on the low voltage (LV) side. 138 kV is chosen as calculation voltage.
ZsA
ZsB
Ztr
f
E
ZlA
ZlB
IEC14000046-1-en.vsd
IEC14000046 V1 EN-US
Figure 37: Thevenin equivalent of the tap transformer
Converting the sources into impedances gives:
Section 4
1MRK 505 382-UEN E
Analog and binary signal transfer for line differential protection
36
Communication set-up, 670/650 series
Application Guide
© Copyright 2017 ABB. All rights reserved