9.8.2.2
Enable forcing using TESTMODE function block
•
Use the TESTMODE function block, appropriately configured in PCM600/ACT.
It may be convenient to control the input on mentioned component from, for example,
an LHMI function key or similar during commissioning to quickly and easily enter
IED test mode.
9.8.3
How to change binary input/output signals using forcing
Once the IED is in IED test mode, the LHMI/PCM600 menus can be used to control
input/output signals freely.
9.8.3.1
Forcing by using LHMI
Editing a signal value directly
•
Edit the input/output value directly to select the desired logical level, by doing
following:
1.
Select the value line of the desired signal, see figure
.
2.
Press the Enter key to edit the value.
IEC15000021 V1 EN
Figure 12:
Value line of the desired signal
3.
Use the up/down arrows on the LHMI to change the signal value or the
appropriate menu in PCM600.
The status of the signal changes automatically to Forced (i.e. there is no
need to set the status to Forced manually).
Section 9
1MRK 506 355-UEN A
Testing IED operation
78
Line distance protection REL670 2.1 IEC
Commissioning manual