The programming of the autorecloser function SMBRREC determines if three-phase
or single-phase trip is initiated as result of the test.
Keep the current constant when measuring operating characteristics. Keep the current
as close as possible to its rated value or lower. But make sure it is higher than the set
minimum operating current.
Ensure that the maximum continuous current in an IED does not exceed four times its
rated value, if the measurement of the operating characteristics runs under constant
voltage conditions.
To verify the mho characteristic, at least two points should be tested.
In the following, three test points are proposed. The mho characteristic always goes
through the origin, which automatically gives a fourth point for the characteristic.
10.4.3.1
Phase-to-phase faults
ZAngPP
ZPP
1
2
3
Ohm/phase
R
X
IEC07000009-4-en.vsd
50%
IEC07000009 V4 EN
Figure 18:
Proposed test points for phase-to-phase fault
Table 21:
Test points for phase-to-phase (ohms / phase)
Test
points
reach
Value
Comments
1
X
ZPP · sin(ZAngPP)
R
ZPP · sin(ZAngPP)
2
X
0,5· (ZPP· sin(ZAngPP)
R
0,5·ZPP + ΔR = 0,5·ZPP·(1+cos(ZAngPP))
3
X
0,5·ZPP·sin(ZAngPP)
R
0,5·ZPP - ΔR = 0,5·ZPP(1-cos(ZAngPP))
Section 10
1MRK 506 355-UEN A
Testing functionality by secondary injection
98
Line distance protection REL670 2.1 IEC
Commissioning manual
Содержание Relion 670 Series REL670
Страница 1: ...Relion 670 series Line distance protection REL670 2 1 IEC Commissioning manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 34: ...28 ...
Страница 64: ...58 ...
Страница 68: ...62 ...
Страница 90: ...84 ...
Страница 254: ...248 ...
Страница 260: ...254 ...
Страница 269: ...263 ...