Check that the service values (VOLTAGE, CURRENT, R(%), X(%) ) are
according to the injected quantities and that ROTORANG is close to 3.14 rad. For
this particular injection the service values are:
•
VOLTAGE = 10.74 kV
•
CURRENT = 20918 A
•
R = 7.37%
•
X = 53.40%
•
ROTORANG = -3.09 rad
Note that these values identify a point inside the lens characteristic, in the zone 2,
that is close to the point RE. The START is issued, but no TRIP is performed.
Execution of the dynamic test
The test may be performed by using two states of a sequence tool that is a basic feature
of test sets.
•
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance,
that is, a point in the plane R-X which is far away from the lens characteristic.
Define the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V
V
V
V
V
ts
t FwdZ
VT s
VT p
=
×
×
=
×
×
=
0 9
0 9 11931
0 1
13 8
77 81
.
.
.
.
.
,
,
,
EQUATION14063 V1 EN
(Equation 31)
∠
=
=
=
V
ForwardX
ForwardR
ts
arctan
arctan
.
.
59 33
8 19
82..14
°
EQUATION14058 V1 EN
(Equation 32)
frequency of V
ts
= 50 Hz
I
50s
= 0 A
I
tfs
= 0 A
•
State 2: main test step.
Section 10
1MRK 506 355-UEN A
Testing functionality by secondary injection
132
Line distance protection REL670 2.1 IEC
Commissioning manual
Содержание Relion 670 Series REL670
Страница 1: ...Relion 670 series Line distance protection REL670 2 1 IEC Commissioning manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 34: ...28 ...
Страница 64: ...58 ...
Страница 68: ...62 ...
Страница 90: ...84 ...
Страница 254: ...248 ...
Страница 260: ...254 ...
Страница 269: ...263 ...