Table 81. Voltage control TCMYLTC and TLCYLTC , continued
Function
Range or value
Accuracy
Time after position change before the value is accepted
(1–60) s
±0.2% or ±200 ms
whichever is greater
Tap changer constant time-out
(1–120) s
±0.2% or ±200 ms
whichever is greater
Raise/lower command output pulse duration
(0.5–10.0) s
±0.2% or ±200 ms
whichever is greater
1MRK 502 068-BEN D
Generator protection REG670 2.1 IEC
Product version: 2.1
86
ABB