Voltage-restrained time overcurrent protection VRPVOC

GUID-935E1CE8-601F-40E2-8D22-2FF68420FADF v6

Voltage-restrained time overcurrent protection (VRPVOC)
function can be used as generator backup protection against
short-circuits.

The overcurrent protection feature has a settable current level
that can be used either with definite time or inverse time
characteristic. Additionally, it can be voltage controlled/
restrained.

One undervoltage step with definite time characteristic is also
available within the function in order to provide functionality
for overcurrent protection with undervoltage seal-in.

Negative sequence time overcurrent protection for machines
NS2PTOC

GUID-DBF3EC07-D947-4483-ABD1-4F7D29F48D61 v6

Negative-sequence time overcurrent protection for machines
NS2PTOC is intended primarily for the protection of
generators against possible overheating of the rotor caused
by negative sequence current in the stator current.

The negative sequence currents in a generator may, among
others, be caused by:

• Unbalanced loads
• Line to line faults
• Line to earth faults
• Broken conductors
• Malfunction of one or more poles of a circuit breaker or a

disconnector

NS2PTOC can also be used as a backup protection, that is,
to protect the generator in case line protections or circuit
breakers fail to clear unbalanced system faults.

To provide an effective protection for the generator for
external unbalanced conditions, NS2PTOC is able to directly
measure the negative sequence current. NS2PTOC also has a
time delay characteristic which matches the heating

characteristic of the generator 

2

2

I t

K

=

 as defined in

standard IEEE C50.13.

where:
I

2

is negative sequence current expressed in

per unit of the rated generator current

t

is operating time in seconds

K

is a constant which depends of the

generators size and design

NS2PTOC has a wide range of 

K

 settings and the sensitivity

and capability of detecting and tripping for negative sequence
currents down to the continuous capability of a generator.

In order to match the heating characteristics of the generator
a reset time parameter can be set.

A separate definite time delayed output is available as an
alarm feature to warn the operator of a potentially dangerous
situation.

Accidental energizing protection for synchronous generator
AEGPVOC

GUID-02AA771D-2DFA-4BEE-92FD-CBF0E0448FBA v6

Inadvertent or accidental energizing of off-line generators has
occurred often enough due to operating errors, breaker head
flashovers, control circuit malfunctions, or a combination of
these causes. Inadvertently energized generator operates as
induction motor drawing a large current from the system. The
voltage supervised overcurrent protection is used to detect
the inadvertently energized generator.

Accidental energizing protection for synchronous generator
(AEGPVOC) takes the maximum phase current input and
maximum phase to phase voltage inputs from the terminal
side. AEGPVOC is enabled when the terminal voltage drops
below the specified voltage level for the preset time.

Stator overload protection GSPTTR

GUID-A416C856-E438-4ED4-A43D-D05F718D6A41 v5

The generator overload function, GSPTTR is used to protect
the stator winding against excessive temperature as a result
of overcurrents. The functions operating characteristic is
designed in accordance with the American standard IEEE-
C50.13.

If internal generator components exceed its design
temperature limit, damage can be the result. Damage to
generator insulation can range from minor loss of life to
complete failure, depending on the severity and duration of
the temperature excursion. Excess temperature can also
cause mechanical damage due to thermal expansion. Since
temperature increases with current, it is logical to apply
overcurrent elements with inverse time characteristics.

For its operation the function either measures the true RMS
current of the stator winding or waited sum of the positive
and negative sequence components in the stator winding.

The function is designed to work on 50/60 Hz systems.

Rotor overload protection GRPTTR

GUID-E3AE6200-DB8D-4C49-A740-09366A333B4F v4

The generator overload function, GRPTTR is used to protect
the rotor winding against excessive temperature as a result of
overcurrents. The functions operating characteristic is
designed in accordance with the American standard IEEE-
C50.13.

If internal generator components exceed its design
temperature limit, damage can be the result. Damage to
generator insulation can range from minor loss of life to
complete failure, depending on the severity and duration of
the temperature excursion. Excess temperature can also
cause mechanical damage due to thermal expansion. Rotor
components such as bars and end rings are vulnerable to this
damage. Since temperature increases with current, it is
logical to apply overcurrent elements with inverse time
characteristics.

1MRK 502 068-BEN D

Generator protection REG670 2.1 IEC

 

Product version: 2.1

 
 

ABB

23

Содержание RELION 670 SERIES REG670

Страница 1: ...Relion 670 series Generator protection REG670 2 1 IEC Product guide...

Страница 2: ...ta 39 21 Ordering for customized IED 112 22 Ordering for pre configured IED 122 23 Ordering for Accessories 127 Disclaimer The information in this document is subject to change without notice and shou...

Страница 3: ...to an operator HMI The wide application flexibility makes this product an excellent choice for both new installations and for refurbishment in existing power plants Forcing of binary inputs and output...

Страница 4: ...SES RSYN 25 SC VC CCS SPVC 87 INd I S SIML 71 ROTI PHIZ 64R R OOS PPAM 78 Ucos HZ PDIF 87 Id SDE PSDE 67N IN T2W PDIF 87T 3Id I STEF PHIZ 59THD U3d N EF4 PTOC 51N_67N 4 IN SA PFRC 81 df dt Other Func...

Страница 5: ...MXU MET I C MSQI MET Isqi C MMXU MET I C MSQI MET Isqi C MMXU MET I C MMXU MET I OC4 PTOC 51_67 4 3I NS2 PTOC 46 I2 C MSQI MET Isqi IEC11000071 5 en vsd SES RSYN 25 SC VC CCS SPVC 87 INd I STTI PHIZ 6...

Страница 6: ...OC4 PTOC 51_67 4 3I OC4 PTOC 51_67 4 3I Y Y Y ROV2 PTOV 59N 2 U0 HV_NCT G C MSQI MET Isqi C MMXU MET I V MMXU MET U V MSQI MET Usqi C MSQI MET Isqi C MMXU MET I T3W PDIF 87T 3Id I FUF SPVC U I REF PDI...

Страница 7: ...2 REFPDIF 87N Restricted earth fault protection low impedance 0 3 1 A01 1 Impedance protection ZMHPDIS 21 Fullscheme distance protection mho characteristic 0 4 3 3 3 ZDMRDIR 21D Directional impedance...

Страница 8: ...ctional overpower protection 0 4 2 4 4 NS2PTOC 46I2 Negative sequence time overcurrent protection for machines 0 2 1 1 1 AEGPVOC 50AE Accidental energizing protection for synchronous generator 0 2 1 1...

Страница 9: ...670 B30 REG670 C30 Multipurpose protection CVGAPC General current and voltage protection 1 12 6 6 6 General calculation SMAIHPAC Multipurpose filter 0 6 1 67 requires voltage 2 67N requires voltage 1M...

Страница 10: ...cation function for Double Point indication 16 16 16 16 SPC8GAPC Single point generic control 8 signals 5 5 5 5 AUTOBITS AutomationBits command function for DNP3 0 3 3 3 3 SINGLECMD Single command 16...

Страница 11: ...conversion 18 18 18 18 BTIGAPC Boolean 16 to Integer conversion with Logic Node representation 16 16 16 16 IB16 Integer to Boolean 16 conversion 18 18 18 18 ITBGAPC Integer to Boolean 16 conversion wi...

Страница 12: ...6 M15 12 M12 12 M12 I103MEAS Measurands for IEC 60870 5 103 1 1 1 1 I103MEASUSR Measurands user defined signals for IEC 60870 5 103 3 3 3 3 I103AR Function status auto recloser for IEC 60870 5 103 1 1...

Страница 13: ...able logic blocks Q T Total number of instances ANDQT 120 INDCOMBSPQT 20 INDEXTSPQT 20 INVALIDQT 22 INVERTERQT 120 ORQT 120 PULSETIMERQT 40 RSMEMORYQT 40 SRMEMORYQT 40 TIMERSETQT 40 XORQT 40 Table 4 T...

Страница 14: ...PFREC DNP3 0 fault records for TCP IP and EIA 485 communication protocol 1 1 1 1 IEC 61850 8 1 Parameter setting function for IEC 61850 1 1 1 1 GOOSEINTLKRCV Horizontal communication via GOOSE for int...

Страница 15: ...1 1 ACTIVLOG Activity logging parameters 1 1 1 1 ALTRK Service Tracking 1 1 1 1 SINGLELCCH Single ethernet port link status 1 1 1 1 PRPSTATUS Dual ethernet port link status 1 1 1 1 Process bus communi...

Страница 16: ...matrix for binary outputs SMMI Signal matrix for mA inputs SMAI1 SMAI12 Signal matrix for analog inputs 3PHSUM Summation block 3 phase ATHSTAT Authority status ATHCHCK Authority check AUTHMAN Authori...

Страница 17: ...the power system close to other generating blocks the fast fault clearance is essential to maintain the transient stability of the non faulted generators Normally the short circuit fault current is ve...

Страница 18: ...ing at high internal fault currents Included is an sensitive differential protection element based on the theory of negative sequence current component This element offers the best possible coverage o...

Страница 19: ...neous faults and faults with only zero sequence in feed During phase to earth faults on heavily loaded power lines there is an adaptive load compensation algorithm that prevents overreaching of the di...

Страница 20: ...of the currents of the two channels I3P1 and I3P2 Loss of excitation LEXPDIS SEMOD151269 4 v8 There are limits for the under excited operation of a synchronous machine A reduction of the excitation c...

Страница 21: ...I inverse time characteristics are available together with an optional user defined time characteristic The directional function needs voltage as it is voltage polarized with memory The function can b...

Страница 22: ...reakers in case the own breaker fails to open CCRBRF can be current based contact based or an adaptive combination of these two conditions A current check with extremely short reset time is used as ch...

Страница 23: ...l energizing of off line generators has occurred often enough due to operating errors breaker head flashovers control circuit malfunctions or a combination of these causes Inadvertently energized gene...

Страница 24: ...stray flux will flow into non laminated components that are not designed to carry flux This will cause eddy currents to flow These eddy currents can cause excessive heating and severe damage to insula...

Страница 25: ...o on Separate definite time delays are provided for operate and restore SAPTUF is provided with undervoltage blocking The operation is based on positive sequence voltage measurement and requires two p...

Страница 26: ...nce with a parameter setting Additionally two overvoltage and two undervoltage steps either with definite time or inverse time characteristic are available within each function The general function su...

Страница 27: ...he weak infeed logic These functions can operate unintentionally if a fault occurs in the secondary circuits between voltage instrument transformers and the IED These unintentional operations can be p...

Страница 28: ...erly select and operate switching primary apparatuses The Switch controller may handle and operate on one three phase device or up to three one phase devices Circuit breaker SXCBR M13489 3 v6 The purp...

Страница 29: ...he command function block has outputs that can be used for example to control high voltage apparatuses or for other user defined functionality 11 Logic Tripping logic SMPPTRC M12275 3 v10 A function b...

Страница 30: ...nused inputs in other function blocks to a certain level value or for creating certain logic Boolean integer floating point string types of signals are available One FXDSIGN function block is included...

Страница 31: ...binary signals The Disturbance report functionality is a common name for several functions Event list Indications Event recorder Trip value recorder Disturbance recorder The Disturbance report functio...

Страница 32: ...neric communication function for Single Point indication SPGAPC SEMOD55713 5 v7 Generic communication function for Single Point indication SPGAPC is used to send one single logical signal to other sys...

Страница 33: ...n for energy calculation and demand handling ETPMMTR uses measured active and reactive power as input and calculates the accumulated active and reactive energy pulses in forward and reverse direction...

Страница 34: ...s extensions of simple substation automation systems but the main use is for Substation Monitoring Systems SMS IEC 60870 5 103 communication protocol SEMOD120137 5 v3 A single glass or plastic port is...

Страница 35: ...e transducers The module has six independent galvanically separated channels Optical ethernet module OEM M16073 3 v6 The optical fast ethernet module is used for fast and interference free communicati...

Страница 36: ...class CT inputs are available Alternative connectors of Ring lug or Compression type can be ordered High impedance resistor unit M16727 3 v2 The high impedance resistor unit with resistors for pick up...

Страница 37: ...losure The SIM module generates a square wave voltage signal for injection into the stator circuit via the neutral point VT NGT The SIM module measures the voltage and current from the injected signal...

Страница 38: ...2803 KB Connection diagram REG670 2 1 C30 1MRK002803 KC Connection diagrams for Customized products Connection diagram 670 series 2 1 1MRK002802 AF Connection diagrams for Injection equipment Connecti...

Страница 39: ...ns according to the specified requirements Energizing quantities rated values and limits IP15765 1 v2 Analog inputs IP15842 1 v1 M16988 1 v9 Table 7 TRM Energizing quantities rated values and limits f...

Страница 40: ...Input resistance Rin 194 Ohm Input range 5 10 20mA 0 5 0 10 0 20 4 20mA Power consumption each mA board each mA input 2 W 0 1 W SEMOD55310 2 v8 Table 10 OEM Optical ethernet module Quantity Rated valu...

Страница 41: ...ms Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range M50609 2 v6 Table 13 BIM Binary input module with enhanced pulse counting capabilitie...

Страница 42: ...V 220 250 V RL 20 RL 20 RL 20 RL 20 Power consumption 24 30 V 50 mA 48 60 V 50 mA 110 125 V 50 mA 220 250 V 50 mA 220 250 V 110 mA max 0 05 W input max 0 1 W input max 0 2 W input max 0 4 W input max...

Страница 43: ...2 Max system voltage 250 V AC DC 250 V DC Test voltage across open contact 1 min 1000 V rms 800 V DC Current carrying capacity Per relay continuous Per relay 1 s Per process connector pin continuous...

Страница 44: ...relays parallel reed relay Binary outputs IOM 10 IOM 2 Max system voltage 250 V AC DC 250 V DC Test voltage across open contact 1 min 250 V rms 250 V rms Current carrying capacity Per relay continuous...

Страница 45: ...0A Breaking capacity for DC with L R 40ms 48V 1A 110V 0 4A 60V 0 75A 125V 0 35A 220V 0 2A 250V 0 15A Operating time 1ms 1ms Table 18 SOM Static Output module data reference standard IEC 61810 2 Electr...

Страница 46: ...5846 1 v1 M16705 1 v9 Table 20 Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature operate value 20 C 10 C to 55 C 0 02 C Relative humidity Operati...

Страница 47: ...20 content 2nd 3rd and 5th harmonic of fr 2 0 Harmonic frequency dependence for high impedance differential protection 10 content 2nd 3rd and 5th harmonic of fr 5 0 Harmonic frequency dependence for...

Страница 48: ...ency immunity test 150 300 V 50 Hz IEC 60255 26 Zone A Conducted common mode immunity test 15 Hz 150 kHz IEC 61000 4 16 Class IV Power frequency magnetic field test 1000 A m 3 s 100 A m cont IEC 61000...

Страница 49: ...ty 93 IEC 60068 2 78 Damp heat test cyclic Test Db for 6 cycles at 25 to 55 C and humidity 93 to 95 1 cycle 24 hours IEC 60068 2 30 Table 26 CE compliance Test According to Immunity EN 60255 26 Emissi...

Страница 50: ...High energy IEC 60255 26 Zone A Power frequency immunity test 150 300 V 50 Hz IEC 60255 26 Zone A Power frequency magnetic field test 1000 A m 3 s 100 A m cont IEC 61000 4 8 Radiated electromagnetic...

Страница 51: ...e test REG670 and REX060 REX061 and REX062 IEC 60255 21 2 Class 1 Class 2 Shock withstand test REG670 and REX060 REX061 and REX062 IEC 60255 21 2 Class 1 Class 2 Bump test REG670 and REX060 REX061 and...

Страница 52: ...2 Table 34 Temperature influence Test Type test values Influence Ambient temperature operate value 25 C to 55 C 0 02 C Storage temperature 40 C to 85 C GUID 52764B12 501B 4B46 9703 E3EB95E06509 v3 Tab...

Страница 53: ...at 2 to 0 x IdMin restrained function Min 10 ms Max 25 ms Operate time at 0 to 5 x IdUnre unrestrained function Min 5 ms Max 15 ms Reset time at 5 to 0 x IdUnre unrestrained function Min 15 ms Max 30...

Страница 54: ...11 Operate time at 0 to 2 x Id restrained function Min 20 ms Max 30 ms Reset time at 2 to 0 x Id restrained function Min 10 ms Max 25 ms Operate time at 0 to 5 x Id unrestrained function Min 10 ms Max...

Страница 55: ...us power U Trip2 SeriesResistor 200 W Operate time at 0 to 10 x Ud Min 5 ms Max 15 ms Reset time at 10 to 0 x Ud Min 75 ms Max 95 ms Critical impulse time 2 ms typically at 0 to 10 x Ud Operate time a...

Страница 56: ...Positive sequence impedance angle Ph E loop 10 90 degrees Reverse reach Ph E loop Magnitude 0 005 3000 000 phase Magnitude of earth return compensation factor KN 0 00 3 00 Angle for earth compensation...

Страница 57: ...5 30 x Ir Angle At 0 degrees and 85 degrees Positive sequence resistance reach Ph E and Ph Ph loop 0 00 1000 00 ohm phase Zero sequence reactance reach 0 01 9000 00 ohm p Zero sequence resistive reach...

Страница 58: ...reach Ph E and Ph Ph 1 00 9000 00 l Dynamic overreach 5 at 85 deg measured with CVT s and 0 5 SIR 30 Definite time delay to trip Ph E and Ph Ph operation 0 000 60 000 s 0 2 or 35 ms whichever is great...

Страница 59: ...enter of the set circle Min 35 ms Max 50 ms GUID 3740D5F1 3245 40EC 89B7 81297A3125D1 v2 Table 46 ROTIPHIZ technical data Function Range or value Accuracy Fault resistance sensitivity Can be reached a...

Страница 60: ...Rf 0 and filter length 1 s 0 00 600 00 s 0 2 or 2 00 s whichever is greater GUID E8104D00 3183 4F55 89F9 A74B14BFE6FE v4 Table 48 Underimpedance protection for generators and transformersZGVPDIS Techn...

Страница 61: ...ase Operate time at 0 to 2 x Iset Min 15 ms Max 25 ms Reset time at 2 to 0 x Iset Min 15 ms Max 25 ms Critical impulse time 10 ms typically at 0 to 2 x Iset Operate time at 0 to 10 x Iset Min 5ms Max...

Страница 62: ...me start non directional at 0 to 2 x Iset Min 15 ms Max 30 ms Reset time start non directional at 2 to 0 x Iset Min 15 ms Max 30 ms Operate time start non directional at 0 to 10 x Iset Min 5 ms Max 20...

Страница 63: ...ble 164 and Table 165 16 curve types See Table 163 Table 164 and Table 165 Second harmonic blocking 5 100 of fundamental 2 0 of Ir Minimum polarizing voltage 1 100 of UBase 0 5 of Ur Minimum polarizin...

Страница 64: ...0 degrees Operate current for directional release 1 100 of IBase For RCA 60 degrees 2 5 of Ir at I Ir 2 5 of I at I Ir Minimum polarizing voltage 1 100 of UBase 0 5 of Ur Minimum polarizing current 2...

Страница 65: ...r at U Ur 0 5 of U at U Ur Operate time for non directional residual overcurrent at 0 to 2 x Iset Min 40 ms Max 65 ms Reset time for non directional residual overcurrent at 2 to 0 x Iset Min 40 ms Max...

Страница 66: ...t I Ir 1 0 of I at I Ir Reset ratio phase current 95 Operate residual current 2 200 of lBase 1 0 of Ir at I Ir 1 0 of I at I Ir Reset ratio residual current 95 Phase current level for blocking of cont...

Страница 67: ...0 0 of SBase When measuring transformer inputs are used the following accuracy can be obtained for low pickup settings which are typical for reverse power protection application 1 0 of Sr at S Sr 1 0...

Страница 68: ...erse Inverse time characteristic step 1 2 2 2 I t K K 1 0 99 0 2 0 or 40 ms whichever is greater Reset time inverse characteristic step 1 2 2 2 I t K Reset Multiplier 0 01 20 00 5 0 or 40 ms whichever...

Страница 69: ...0 to 2 x Iset 0 000 60 000 s 0 2 or 35 ms whichever is greater Definite time delay undervoltage at 1 2 x Uset to 0 8 x Uset 0 000 60 000 s 0 2 or 35 ms whichever is greater Definite time delay overvo...

Страница 70: ...50 13 2005 1 5 or 200 ms whichever is greater Minimum operate time for thermal characteristic 1 0 120 0 s 1 5 or 200 ms whichever is greater Maximum operate time for thermal characteristic 100 0 2000...

Страница 71: ...00 00 s 0 2 or 40ms whichever is greater Definite time delay step 2 at 1 2 to 0 x Uset 0 000 60 000 s 0 2 or 40ms whichever is greater Minimum operate time inverse characteristics 0 000 60 000 s 0 5 o...

Страница 72: ...chever is greater Definite time delay high step step 2 at 0 to 1 2 x Uset 0 000 60 000 s 0 2 or 45 ms whichever is greater Minimum operate time Inverse characteristics 0 000 60 000 s 0 2 or 45 ms whic...

Страница 73: ...e time start at 0 to 1 2 x Uset Min 20 ms Max 35 ms Reset time start at 1 2 to 0 x Uset Min 5 ms Max 25 ms Critical impulse time 10 ms typically at 0 to 2 x Uset Impulse margin time 15 ms typically M1...

Страница 74: ...ver is greater SEMOD175168 2 v7 Table 69 100 Stator E F 3rd harmonic STEFPHIZ Function Range or value Accuracy Fundamental frequency level UN 95 Stator EF 1 0 50 0 of UBase 0 25 of Ur Third harmonic d...

Страница 75: ...se UMin 50 150 of Ubase Exponent 0 0 5 0 tMax 0 010 60 000 s tMin 0 010 60 000 s 1 0 or 120 ms whichever is greater Exponent U UMin t tMax tMin tMin UNom UMin EQUATION1182 V1 EN US Equation 3 U Umeasu...

Страница 76: ...nge or value Accuracy Operate value frequency high limit level at symmetrical three phase voltage 35 00 90 00 Hz 2 0 mHz Operatevalue frequency low limit level at symmetrical three phase voltage 30 00...

Страница 77: ...Multipurpose protection M13095 2 v7 1MRK 502 068 BEN D Generator protection REG670 2 1 IEC Product version 2 1 ABB 77...

Страница 78: ...ater Overcurrent non directional Start time at 0 to 2 x Iset Min 15 ms Max 30 ms Reset time at 2 to 0 x Iset Min 15 ms Max 30 ms Start time at 0 to 10 x Iset Min 5 ms Max 20 ms Reset time at 10 to 0 x...

Страница 79: ...nt operation step 1 2 1 0 200 0 of UBase 1 0 of Ur at U Ur 1 0 of U at U Ur Directional function Settable NonDir forward and reverse Relay characteristic angle 180 to 180 degrees 2 0 degrees Relay ope...

Страница 80: ...60 Hz Supply voltage 120 or 230 V 50 60 Hz Operate earth fault resistance value Approx 1 20 k Influence of harmonics in the DC field voltage Negligible influence of 50 V 150 Hz or 50 V 300 Hz Permitte...

Страница 81: ...s See tables 163 and 164 Minimum operate time for inverse time characteristics 0 00 60 00 s 0 2 or 35 ms whichever is greater High voltage limit voltage dependent operation 30 0 100 0 of UBase 1 0 of...

Страница 82: ...current zero sequence 1 100 of IBase 0 5 of Ir Operate voltage negative sequence 1 100 of UBase 0 5 of Ur Operate current negative sequence 1 100 of IBase 0 5 of Ir Operate voltage change level 1 100...

Страница 83: ...failure at 1 to 0 x Ur Min 5 ms Max 15 ms Reset time block of main fuse failure at 0 to 1 x Ur Min 15 ms Max 30 ms Operate value alarm for pilot fuse failure 10 0 80 0 of UBase 0 5 of Ur Reset ratio...

Страница 84: ...0 Hz 2 5 mHz Breaker closing pulse duration 0 050 60 000 s 0 2 or 15 ms whichever is greater tMaxSynch which resets synchronizing function if no close has been made before set time 0 000 6000 00 s 0 2...

Страница 85: ...age auto correction 20 0 20 0 of UBase Duration time for the reverse action block signal 30 6000 s 0 2 or 600 ms whichever is greater Current limit for reverse action block 0 100 of I1Base Overcurrent...

Страница 86: ...before the value is accepted 1 60 s 0 2 or 200 ms whichever is greater Tap changer constant time out 1 120 s 0 2 or 200 ms whichever is greater Raise lower command output pulse duration 0 5 10 0 s 0...

Страница 87: ...nces Function Quantity with cycle time 3 ms 8 ms 100 ms TMAGAPC 6 6 GUID A05AF26F DC98 4E62 B96B E75D19F20767 v1 Table 85 Number of ALMCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms...

Страница 88: ...23E7 4816 84F2 1FBFFDFF2B43 v1 Table 93 Number of PULSETIMER instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms PULSETIMER 10 10 20 0 000 90000 000 s 0 5 10 ms GUI...

Страница 89: ...ms 100 ms INDEXTSPQT 10 10 GUID 77FEBE9B 0882 4E85 8B1A 7671807BFC02 v1 Table 101 Number of INVALIDQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INVALIDQT 6 6 GUID F25B94C6 9CC9...

Страница 90: ...000 90000 000 s 0 5 10 ms GUID 1C381E02 6B9E 44DC 828F 8B3EA7EDAA54 v1 Table 108 Number of XORQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms XORQT 10 30 GUID 19810098 1820 4765 8F...

Страница 91: ...s whichever is greater Time integration continuous active 8 0 999999 99 s 0 2 or 50 ms whichever is greater Table 114 IntegratorTIGAPC continued Function Cycle time ms Range of value Accuracy Time int...

Страница 92: ...Running hour meter TEILGAPC Function Range or value Accuracy Time limit for alarm supervision tAlarm 0 99999 9 hours 0 1 of set value Time limit for warning supervision tWarning 0 99999 9 hours 0 1 o...

Страница 93: ...5 of Sr at S 0 5 x Sr 0 5 of S at S 0 5 x Sr 100 to 220 V 0 5 2 0 x Ir 0 2 of S Power factor cos 10 to 300 V 0 1 4 0 x Ir 0 02 100 to 220 V 0 5 2 0 x Ir 0 01 GUID 5E04B3F9 E1B7 4974 9C0B DE9CD4A2408F...

Страница 94: ...0 5 Ir 0 5 degrees at 0 5 Ir I 4 0 Ir GUID 47094054 A828 459B BE6A D7FA1B317DA7 v5 Table 124 Voltage sequence measurement VMSQI Function Range or value Accuracy Voltage positive sequence U1 10 to 300...

Страница 95: ...g rate 1 kHz at 50 Hz 1 2 kHz at 60 Hz Recording bandwidth 5 300 Hz GUID F034B396 6600 49EF B0A5 8ED96766A6A0 v6 Table 127 Insulation gas monitoring function SSIMG Function Range or value Accuracy Pre...

Страница 96: ...460E B02F C7D4F1937432 v7 Table 129 Breaker monitoring SSCBR Function Range or value Accuracy Alarm level for open and close travel time 0 200 ms 3 ms Alarm level for number of operations 0 9999 Inde...

Страница 97: ...4 Disturbance recorder Function Value Buffer capacity Maximum number of analog inputs 40 Maximum number of binary inputs 128 Maximum number of disturbance reports 100 Maximum total recording time 3 4...

Страница 98: ...odule BIM Cycle time for report of counter value 1 3600 s SEMOD153707 2 v4 Table 137 Energy metering ETPMMTR Function Range or value Accuracy Energy metering kWh Export Import kvarh Export Import Inpu...

Страница 99: ...ion protocol Function Value Protocol LON Communication speed 1 25 Mbit s M11901 1 v2 Table 141 SPA communication protocol Function Value Communication speed 300 1200 2400 4800 9600 19200 or 38400 Bd S...

Страница 100: ...antity Range or value Connector X 21 Micro D sub 15 pole male 1 27 mm 0 050 pitch Connector ground selection 2 pole screw terminal Standard CCITT X21 Communication speed 64 kbit s Insulation 1 kV Maxi...

Страница 101: ...distance about 2 km 1 mile 22 dB typical distance 80 km 50 mile 26 dB typical distance 110 km 68 mile Optical connector Type ST Type FC PC Type FC PC Protocol C37 94 C37 94 implementation C37 94 imple...

Страница 102: ...ally only non conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected Connection system SEMOD53371 1 v1 SEMOD53376 2 v6 Table 153 CT and...

Страница 103: ...ategory III Pollution degree 2 GUID CDBAEE7B 3BCE 4401 B2DA BF572CFF9DAE v3 Table 156 Coupling capacitor unit REX061 Function Range or values Accuracy For machines with rated field voltage up to 800 V...

Страница 104: ...4 5 kg Assembling 6 x 5 mm screws 3 at bottom and 3 at top Rated stator injection voltage 240 V Rated stator voltage 240 V Burden injection X1 2 and X1 4 25 VA at 12 V earth fault voltage 100 VA at 24...

Страница 105: ...OD55660 2 v3 Table 160 GPS time synchronization module GTM Function Range or value Accuracy Receiver 1 s relative UTC Time to reliable time reference with antenna in new position or after power loss l...

Страница 106: ...e modulated low level high level 1 3 Vpp 3 x low level max 9 Vpp Supported formats IRIG B 00x IRIG B 12x Accuracy 10 s for IRIG B 00x and 100 s for IRIG B 12x Input impedance 100 k ohm Optical connect...

Страница 107: ...C37 112 2 0 or 40 ms whichever is greater ANSI Extremely Inverse A 28 2 B 0 1217 P 2 0 tr 29 1 ANSI Very inverse A 19 61 B 0 491 P 2 0 tr 21 6 ANSI Normal Inverse A 0 0086 B 0 0185 P 0 02 tr 0 46 ANSI...

Страница 108: ...t k I CR EQUATION1253 SMALL V1 EN US I Imeasured Iset k 0 05 999 in steps of 0 01 A 0 005 200 000 in steps of 0 001 B 0 00 20 00 in steps of 0 01 C 0 1 10 0 in steps of 0 1 P 0 005 3 000 in steps of 0...

Страница 109: ...EQUATION1437 SMALL V2 EN US k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 32 0 5 0 035 t k U U U EQUATION1438 SMALL V2 EN US k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQU...

Страница 110: ...0 055 32 0 5 k t U U U EQUATION1432 SMALL V1 EN US U Uset U Umeasured k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATION1433 SMALL V1 EN US U Uset U Umeasured k 0 05 1 10 in...

Страница 111: ...TION1437 SMALL V2 EN US k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 32 0 5 0 035 t k U U U EQUATION1438 SMALL V2 EN US k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATIO...

Страница 112: ...MB B A3X0 D1D1ARGN1N1XXXXXXX AAFXXX AX Product definition Differential protection REG670 2 1 X00 A 0 0 0 0 0 0 0 0 0 Impedance protection B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Current protection C 00 0 0 0...

Страница 113: ...y Notes and rules Alternative 3 Fullscheme distance protection mho characteristic ZMHPDIS 1MRK005907 FA 6 0 4 Directional impedance element for mho characteristic ZDMRDIR 1MRK005907 HA 8 0 2 Alternati...

Страница 114: ...MRK005910 ZB 22 0 1 Rotor overload protection GRPTTR 1MRK005910 YB 23 0 1 Table 179 Voltage protection Position 1 2 3 4 5 6 7 8 D 0 0 Table 180 Voltage functions Function Function identification Order...

Страница 115: ...ted Qty Notes and rules Synchrocheck energizing check and synchronizing SESRSYN 1MRK005917 XA 2 0 2 Apparatus control for up to 6 bays max 30 app 6CBs incl Interlocking APC30 1MRK005917 CY 7 0 1 Tap c...

Страница 116: ...Casing Selection Notes and Rules 1 2 x 19 case A 3 4 x 19 case 1 TRM slot B 3 4 x 19 case 2 TRM slots C 1 1 x 19 case 1 TRM slot D 1 1 x 19 case 2 TRM slots E Selected Table 200 Mounting selection Mo...

Страница 117: ...Table 203 Human machine interface selection Human machine hardware interface Selection Notes and Rules Medium size graphic display IEC keypad symbols B Medium size graphic display ANSI keypad symbols...

Страница 118: ...z 17 First TRM 3IM 5A 4IP 5A 5U 110 220V 50 60Hz 18 First TRM 10I 2U 1A 110 220V 50 60 Hz 19 First TRM 10I 2U 5A 110 220V 50 60 Hz 20 No second TRM included X0 Compression terminals A Ringlug terminal...

Страница 119: ...type BOM SOM and MIM 1 1 x 19 two 2 TRM 11 6 4 4 11 cards including a combination of four cards of type BOM SOM and MIM 3 4 x 19 one 1 TRM 8 6 4 4 8 cards including a combination of four cards of typ...

Страница 120: ...g F F F F F F F F F F F F F F BIMp 16 inputs RL48 60 VDC 30 mA for pulse counting G G G G G G G G G G G G G G BIMp 16 inputs RL110 125 VDC 30 mA for pulse counting H H H H H H H H H H H H H H BIM 16 i...

Страница 121: ...n board included X X X X X X Optical short range LDCM A A A A A A Note Max 4 LDCM same or different type can be selected in configuration F00 Max 2 LDCM in configuration N00 9 2 Rule Always place LDCM...

Страница 122: ...d Rules No option X00 All fields in the ordering form do not need to be filled in Restricted earth fault protection low impedance A01 Note A01 only for B30 High impedance differential protection 3 blo...

Страница 123: ...19 case C Note Only for B30 and C30 Wall mounting kit D Note Wall mounting not recommended with communication modules with fibre connection SLM OEM LDCM Flush mounting kit E Flush mounting kit IP54 m...

Страница 124: ...60 Hz 100 220V 14 Note Only for A20 First TRM 3I 5A 4I 1A 5U 50 60 Hz 100 220V 15 Note Only for A20 No second TRM included X0 Note B30 C30 must include a second TRM Compression terminals A Ringlug te...

Страница 125: ...30 mA for pulse counting F F F F F F F F F BIMp 16 inputs RL48 60 VDC 30 mA for pulse counting G G G G G G G G G BIMp 16 inputs RL110 125 VDC 30 mA for pulse counting H H H H H H H H H BIM 16 inputs...

Страница 126: ...me board to support redundant communication in P30 2 and P30 3 P31 2 and P31 3 or P32 2 and P32 3 Optical medium range LDCM 1310 nm B B B B B B IRIG B Time synchronization module F F F F F F Galvanic...

Страница 127: ...ons for three winding transformers in single or multi breaker arrangement ordering number RK926 315 BD Two winding transformer with external neutral on current circuits Two pcs can be used in applicat...

Страница 128: ...ltage dependent resistor for 20 100V operating voltage Quantity RK 795 101 MB High impedance resistor unit 1 ph with resistor and voltage dependent resistor for 100 400V operating voltage Quantity 1 2...

Страница 129: ...condary side of the VT The VT must have a rating of at least 100 VA and a rated secondary winding voltage of up to 120 V It must adhere to IEC 61869 3 2011 section 5 5 301 Rated Output Values and the...

Страница 130: ...ive resistor on plate Quantity RK795102 AD Configuration and monitoring tools IP15162 1 v2 M15042 3 v3 Front connection cable between LCD HMI and PC Quantity 1MRK 001 665 CA SEMOD131414 4 v3 LED Label...

Страница 131: ...ual IEC 61850 Edition 2 IEC Quantity 1MRK 511 350 UEN Communication protocol manual IEC 60870 5 103 IEC Quantity 1MRK 511 351 UEN Communication protocol manual LON IEC Quantity 1MRK 511 352 UEN Commun...

Страница 132: ...UUS Type test certificate IEC 1MRK 502 068 TEN ANSI 1MRK 502 068 TUS 670 series manuals Document numbers Operation manual IEC 1MRK 500 123 UEN ANSI 1MRK 500 123 UUS Engineering manual IEC 1MRK 511 35...

Страница 133: ...133...

Страница 134: ...notice ABB AB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and i...

Отзывы: