Table 22. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Within nominal range
Influence
Frequency dependence, operate value
f
r
±2.5 Hz for 50 Hz
f
r
±3.0 Hz for 60 Hz
±1.0% / Hz
Frequency dependence for distance protection operate value
f
r
±2.5 Hz for 50 Hz
f
r
±3.0 Hz for 60 Hz
±2.0% / Hz
Harmonic frequency dependence (20% content)
2
nd
, 3
rd
and 5
th
harmonic of f
r
±2.0%
Harmonic frequency dependence for high impedance differential
protection (10% content)
2nd, 3rd and 5
th
harmonic of f
r
±5.0%
Harmonic frequency dependence for high impedance differential
protection (10% content)
2
nd
, 3rd and 5
th
harmonic of f
r
±10.0%
Harmonic frequency dependence for overcurrent protection
2
nd
, 3
rd
and 5
th
harmonic of f
r
±3.0% / Hz