Section 6
Establishing connection and
verifying the SPA/IEC
communication
6.1
Entering settings
M11735-2 v2
If the IED is connected to a monitoring or control system via the rear SPA/IEC103 port, the
SPA/IEC103 port has to be set either for SPA or IEC103 use.
6.1.1
Entering SPA settings
M11735-7 v6
The SPA/IEC port is located on the rear side of the IED. Two types of interfaces can be used:
•
plastic fibers with connector type HFBR
•
glass fibers with connector type ST
When using the SPA protocol, the rear SPA/IEC port must be set for SPA use.
Procedure:
1.
Set the port for SPA use on the local HMI under Main menu /Configuration /
Communication /Station communication/Port configuration/SLM optical serial port/
PROTOCOL:1. When the communication protocol is selected, the IED is automatically
restarted, and the port then operates as a SPA port.
2.
Set the
SlaveAddress and BaudRate for the rear SPA port on the local HMI under Main
menu/Configuration/Communication/Station communication/SPA/SPA:1. Use the
same settings for these as is set in the SMS system for the IED.
6.1.2
Entering IEC settings
M11735-32 v6
The SPA/IEC port is located on the rear side of the IED. Two types of interfaces can be used:
•
plastic fibers with connector type HFBR
•
glass fibers with connector type ST
When using the IEC protocol, the rear SPA/IEC port must be set for IEC use.
Procedure:
1.
Set the port for IEC use on the local HMI under Main menu /Configuration /
Communication /Station communication/Port configuration/SLM optical serial port/
PROTOCOL:1. When the communication protocol is selected, the IED is automatically
restarted, and the port then operates as an IEC port.
2.
Set the
SlaveAddress and BaudRate for the rear IEC port on the local HMI under Main
menu/Configuration/Communication/Station communication/IEC60870-5-103/
OPTICAL103:1. Use the same settings for these as is set in the SMS system for the IED.
1MRK 505 385-UEN C
Section 6
Establishing connection and verifying the SPA/IEC communication
Breaker protection REQ650
39
Commissioning manual
© Copyright 2017 ABB. All rights reserved
Содержание RELION 650 SERIES
Страница 1: ...Relion 650 SERIES Breaker protection REQ650 Version 2 2 IEC Commissioning manual...
Страница 2: ......
Страница 20: ...14...
Страница 24: ...18...
Страница 32: ...26...
Страница 42: ...36...
Страница 48: ...42...
Страница 52: ...46...
Страница 64: ...58...
Страница 118: ...112...
Страница 126: ...120...
Страница 127: ...121...