DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
c_dINC
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
IvdCrv
v1_dSPS
stVal
ST
-
INVAL_CRV
Mon
Invalid curve parameters
q
ST
-
INVAL_CRV
Mon
Quality: Invalid curve parameters
t
ST
-
INVAL_CRV
Mon
Timestamp: Invalid curve
parameters
StrDur
v2_dMV
mag.f
MX
-
START_DUR
Mon
Ratio of start time / operate time
q
MX
-
START_DUR
Mon
Quality: Ratio of start time /
operate time
t
MX
-
START_DUR
Mon
Timestamp: Ratio of start time /
operate time
Table 56:
DPHLPDOC Logical node data (instance 1)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Dir
a_dACD
dirGeneral
ST
-
DIRECTION
Mon
Direction information, general
dirPhsA
ST
-
DIR_A
Mon
Direction information, phase A
dirPhsB
ST
-
DIR_B
Mon
Direction information, phase B
dirPhsC
ST
-
DIR_C
Mon
Direction information, phase C
q
ST
-
DIRECTION
Mon
Quality: Direction information,
general
t
ST
-
DIRECTION
Mon
Timestamp: Direction information,
general
Beh
a_dINS
stVal
ST
-
Beh
Mon
Behaviour parameter for 61850
q
ST
-
Beh
Mon
Quality: Behaviour parameter for
61850
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
for 61850
Mod
c_dINC
stVal
ST
-
-
Mon
Mode status parameter for 61850
q
ST
-
-
Mon
Quality: Mode status parameter for
61850
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
Table 57:
DPHLPDOC Logical node data (instance 1)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
Oper.ctlVal
CO
-
-
Cmd
Mode parameter for 61850
Oper.origin.orCat
CO
-
-
Cmd
Mode parameter for 61850
Oper.origin.orIdent
CO
-
-
Cmd
Mode parameter for 61850
Oper.ctlNum
CO
-
-
Cmd
Mode parameter for 61850
Oper.T
CO
-
-
Cmd
Mode parameter for 61850
Table continues on next page
Section 7
1MRS756793 E
Logical node data model
102
630 series
Communication Protocol Manual