DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
c_dINC
t
ST
-
-
Mon
Timestamp: Mode status value
parameter for 61850
StUpCnt
v1_dINS
stVal
ST
-
START_CNT
Mon
Number of motor start-ups
occurred
q
ST
-
START_CNT
Mon
Quality: Number of motor start-ups
occurred
t
ST
-
START_CNT
Mon
Timestamp: Number of motor
start-ups occurred
RsStUpCnt
v1_dSPC
Oper.ctlVal
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orCat
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orIdent
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.ctlNum
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.T
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.Test
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.Check
CO
-
-
Cmd
Command parameter for
IEC61850
stVal
ST
-
-
Mon
Reset acknowledge for startup
counter
q
ST
-
-
Mon
Quality: Reset acknowledge for
startup counter
t
ST
-
-
Mon
Timestamp: Reset acknowledge
for startup counter
TmsCumStUp
v2_dMV
mag.f
MX
-
T_ST_CNT
Mon
Cumulated start-up time in sec
q
MX
-
T_ST_CNT
Mon
Quality: Cumulated start-up time in
sec
t
MX
-
T_ST_CNT
Mon
Timestamp: Cumulated start-up
time in sec
TmsStUp
v2_dMV
mag.f
MX
-
START_TIME
Mon
Measured motor latest startup
time in sec
q
MX
-
START_TIME
Mon
Quality: Measured motor latest
startup time in sec
t
MX
-
START_TIME
Mon
Timestamp: Measured motor
latest startup time in sec
ThmStsPct
v2_dMV
mag.f
MX
-
IIT_RL
Mon
Thermal stress relative to set
maximum thermal stress
q
MX
-
IIT_RL
Mon
Quality: Thermal stress relative to
set maximum thermal stress
t
MX
-
IIT_RL
Mon
Timestamp: Thermal stress
relative to set maximum thermal
stress
Section 7
1MRS756793 E
Logical node data model
112
630 series
Communication Protocol Manual