![ABB Relion 620 Series Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/abb/relion-620-series/relion-620-series_manual_3414585050.webp)
Section 3
1MAC302441-MB A
IEC 60870-5-101/104 protocol implementation
44
RER620
Point List Manual
Process information in control direction
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
System information in monitor direction
(station-specific parameter, mark with an “X” if it is only used in the standard direction,
“R” if only used in the reverse direction, and “B” if used in both directions)
System information in control direction
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
Parameter in control direction
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
File transfer
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
X
<45>
:= Single command
C_SC_NA_1
X
<46>
:= Double command
C_DC_NA_1
<47>
:= Regulating step command
C_RC_NA_1
<48>
:= Set point command, normalized value
C_SE_NA_1
<49>
:= Set point command, scaled value
C_SE_NB_1
<50>
:= Set point command, short floating point value
C_SE_NC_1
<51>
:= Bitstring of 32 bit
C_BO_NA_1
<70>
:= End of initialization
M_EI_NA_1
X
<100>
:= Interrogation command
C_IC_NA_1
X
<101>
:= Counter interrogation command
C_CI_NA_1
<102>
:= Read command
C_RD_NA_1
X
<103>
:= Clock synchronization command
C_CS_NA_1
<104>
:= Test command
C_TS_NB_1
<105>
:= Reset process command
C_RP_NC_1
X
<106>
:= Delay acquisition command
C_CD_NA_1
<110>
:= Parameter of measured value, normalized value
P_ME_NA_1
<111>
:= Parameter of measured value, scaled value
P_ME_NB_1
<112>
:= Parameter of measured value, short floating point value
P_ME_NC_1
<113>
:= Parameter activation
P_AC_NA_1
<120>
:= File ready
F_FR_NA_1
<121>
:= Section ready
F_SR_NA_1
<122>
:= Call directory, select file, call file, call section
F_SC_NA_1
<123>
:= Last section, last segment
F_LS_NA_1
<124>
:= Ack file, ack section
F_AF_NA_1
<125>
:= Segment
F_SG_NA_1
<126>
:= Directory
F_DR_TA_1
Содержание Relion 620 Series
Страница 2: ......
Страница 8: ...Table of contents 1MAC302441 MB A 2 RER620 Point List Manual...
Страница 16: ...Section 1 1MAC302441 MB A Introduction 10 RER620 Point List Manual...
Страница 44: ...Section 2 1MAC302441 MB A IEC 60870 5 101 104 data mappings 38 RER620 Point List Manual...
Страница 58: ...Section 4 1MAC302441 MB A Glossary 52 RER620 Point List Manual...
Страница 59: ......