Section 3
IEC 60870-5-101/104 protocol implementation
RER620
43
Point List Manual
Selection of standard ASDUs
Process information in monitor direction
(station-specific parameter, mark each type ID with an “X” if it is only used in the standard
direction, “R” if only used in the reverse direction, and “B” if used in both directions)
Either ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, <19>
or of the set <30 –40> are used.
X
<1>
:= Single-point information
M_SP_NA_1
X
<2>
:= Single-point information with time tag
M_SP_TA_1
X
<3>
:= Double-point information
M_DP_NA_1
X
<4>
:= Double-point information with time tag
M_DP_TA_1
<5>
:= Step position information
M_ST_NA_1
<6>
:= Step position information with time tag
M_ST_TA_1
<7>
:= Bitstring of 32 bit
M_BO_NA_1
<8>
:= Bitstring of 32 bit with time tag
M_BO_TA_1
X
<9>
:= Measured value, normalized value
M_ME_NA_1
X
<10>
:= Measured value, normalized value with time tag
M_ME_TA_1
X
<11>
:= Measured value, scaled value
M_ME_NB_1
X
<12>
:= Measured value, scaled value with time tag
M_ME_TB_1
X
<13>
:= Measured value, short floating point value
M_ME_NC_I
X
<14>
:= Measured value, short floating point value with time tag
M_ME_TC_1
X
<15>
:= Integrated totals
M_IT_NA_1
X
<16>
:= Integrated totals with time tag
M_IT_TA_1
<17>
:= Event of protection equipment with time tag
M_EP_TA_1
X
<18>
:= Packed start events of protection equipment with time tag
M_EP_TB_1
X
<19>
:= Packed output circuit information of protection equipment with time tag
M_EP_TC_1
<20>
:= Packed single-point information with status change detection
M_PS_NA_1
X
<21>
:= Measured value, normalized value without quality descriptor
M_ME_ND_1
X
<30>
:= Single-point information with time tag CP56Time2a
M_SP_TB_1
X
<31>
:= Double-point information with time tag CP56Time2A
M_DP_TB_1
<32>
:= Step position information with time tag CP56Time2A
M_ST_TB_1
<33>
:= Bitstring of 32 bit with time tag CP56Time2A
M_BO_TB_1
X
<34>
:= Measured value, normalized value with time tag CP56Time2A
M_ME_TD_1
X
<35>
:= Measured value, scaled value with time tag CP56Time2A
M_ME_TE_1
X
<36>
:= Measured value, short floating point value with time tag CP56Time2A
M_ME_TF_1
X
<37>
:= Integrated totals with time tag CP56Time2A
M_IT_TB_1
<38>
:= Event of protection equipment with time tag CP56Time2A
M_EP_TD_1
X
<39>
:= Packed start events of protection equipment with time tag CP56time2A
M_EP_TE_1
X
<40>
:= Packed output circuit information of protection equipment with time tag
CP56Time2a
M_EP_TF_1
Содержание Relion 620 Series
Страница 2: ......
Страница 8: ...Table of contents 1MAC302441 MB A 2 RER620 Point List Manual...
Страница 16: ...Section 1 1MAC302441 MB A Introduction 10 RER620 Point List Manual...
Страница 44: ...Section 2 1MAC302441 MB A IEC 60870 5 101 104 data mappings 38 RER620 Point List Manual...
Страница 58: ...Section 4 1MAC302441 MB A Glossary 52 RER620 Point List Manual...
Страница 59: ......