Section 1
1MAC302441-MB A
Introduction
8
RER620
Point List Manual
Zero sequence overvoltage protection, source 2
ROVPTOV2
Uo>(2)
59N-2
Frequency Protection
Underfrequency, Overfrequency, Frequency rate of change, source1
FRPFRQ1
f</f>,df/dt(1)
81-1
Underfrequency, Overfrequency, Frequency rate of change, source 2
FRPFRQ2
f</f>,df/dt(2)
81-2
Load Shed & Restoration, source1
LSHDPFRQ1
UFLS/R(1)
81S-1
Load Shed & Restoration, source 2
LSHDPFRQ2
UFLS/R(2)
81S-2
Other Protection
High Impedance Fault Detector
PHIZ1
PHIZ1
HIZ
Circuit breaker failure protection
SCCBRBRF1
3I>/Io>BF
50BFT
Circuit breaker close failure protection
SCCBRBCF1
SCCBRBCF1
50BFC
Directional positive sequence power protection
DPSRDIR1
P>->
32P
Directional negative/zero sequence power protection
DNZSRDIR1
Q>->
32N
Control
Autoreclosing, 1ph and/or 3ph
SDARREC1
O -> I
79
Synch-check/voltage check
SECRSYN1
SYNC
25
Circuit Breaker 1 (3 state inputs / 3 control outputs)
SCBXCBR1
I<->O CB
52
Loop control
DLCM
DLCM
DLCM
Supervision and Monitoring
CB condition monitoring
SPSCBR1
CBCM
52CM
Fuse failure supervision
SEQRFUF1
FUSEF
60
Measurement
Three-phase current
CMMXU1
3I
IA,IB,IC
Demand metering, Max/Min metering
CSMTA1
Sequence current
CSMSQI1
I1,I2,I0
I1, I2, I0
Ground current
RESCMMXU1
Io
IG
Three-phase voltage, source
VMMXU1
3U
VA,VB,VC
Three-phase voltage, load
VMMXU2
3U(B)
VA,VB,VC(2)
Sequence voltages, Source
VSMSQI1
U1,U2,U0
V1,V2,V0
Sequence voltages, Load
VSMSQI2
U1,U2,U0(B)
V1,V2,V0(2)
Three-phase power and energy (incl. cos j)
PEMMXU1
P,E
P,E
Frequency
FMMXU1
f
f
Recorders
Digital fault recorder (DFR)
RDRE1
DR
DFR
Sequence of Events (SER)
SER
SER
SER
Fault Recorder
FLTMSTA
FLTMSTA
FLTMSTA
Fault Locator (FLOC)
DRFLO1
FLO
FLO
Other Functions
Battery voltage, current. Test the battery
ZBAT1
UPS
UPS
Universal Power Drive
XGGIO115
X115(UPD)
X115(UPD)
Programmable buttons (16 buttons)
FKEYGGIO1
FKEYGGIO1
FKEYGGIO1
Move function block (8 outputs)
MVGAPC1
MVGAPC1
MVGAPC1
Function
IEC61850
IEC60617
ANSI/C37.2
Содержание Relion 620 Series
Страница 2: ......
Страница 8: ...Table of contents 1MAC302441 MB A 2 RER620 Point List Manual...
Страница 16: ...Section 1 1MAC302441 MB A Introduction 10 RER620 Point List Manual...
Страница 44: ...Section 2 1MAC302441 MB A IEC 60870 5 101 104 data mappings 38 RER620 Point List Manual...
Страница 58: ...Section 4 1MAC302441 MB A Glossary 52 RER620 Point List Manual...
Страница 59: ......