![ABB Relion 620 Series Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/abb/relion-620-series/relion-620-series_manual_3414585032.webp)
Section 2
1MAC302441-MB A
IEC 60870-5-101/104 data mappings
26
RER620
Point List Manual
SDARREC1.Op.phsA
1111
79:phase A trip
SDARREC1.Op.phsB
1112
79:phase B trip
SDARREC1.Op.phsC
1113
79:phase C trip
SDARREC1.OpOpn.phsA
1114
79:phase A
Yes
SDARREC1.OpOpn.phsB
1115
79:phase B
Yes
SDARREC1.OpOpn.phsC
1116
79:phase C
Yes
SDPHLPTOC1.Op.general
1117
67/51P-1:general trip
SDPHLPTOC1.Op.phsA
1118
67/51P-1:phase A trip
SDPHLPTOC1.Op.phsB
1119
67/51P-1:phase B trip
SDPHLPTOC1.Op.phsC
1120
67/51P-1:phase C trip
SDPHLPTOC1.Str.general
1121
67/51P-1:general pickup
Yes
SDPHLPTOC1.Str.phsA
1122
67/51P-1:phase A pickup
Yes
SDPHLPTOC1.Str.phsB
1123
67/51P-1:phase B pickup
Yes
SDPHLPTOC1.Str.phsC
1124
67/51P-1:phase C pickup
Yes
SDPHLPTOC2.Op.general
1125
67/51P-2:general trip
SDPHLPTOC2.Op.phsA
1126
67/51P-2:phase A trip
SDPHLPTOC2.Op.phsB
1127
67/51P-2:phase B trip
SDPHLPTOC2.Op.phsC
1128
67/51P-2:phase C trip
SDPHLPTOC2.Str.general
1129
67/51P-2:general pickup
Yes
SDPHLPTOC2.Str.phsA
1130
67/51P-2:phase A pickup
Yes
SDPHLPTOC2.Str.phsB
1131
67/51P-2:phase B pickup
Yes
SDPHLPTOC2.Str.phsC
1132
67/51P-2:phase C pickup
Yes
SECRSYN1.FailCmd.stVal
1134
25:FailCmd status
Yes
SECRSYN1.FailSyn.stVal
1135
25:FailSyn status
Yes
SECRSYN1.SynPrg.stVal
1136
25:SynPrg status
Yes
SEQRFUF1.Str.general
1137
60:general pickup
Yes
SEQRFUF1.Str3Ph.general
1138
60:general
Yes
SPHHPTOC1.Op.general
1139
SPHHPTOC1:general trip
SPHHPTOC1.Op.phsA
1140
SPHHPTOC1:phase A trip
SPHHPTOC1.Op.phsB
1141
SPHHPTOC1:phase B trip
SPHHPTOC1.Op.phsC
1142
SPHHPTOC1:phase C trip
SPHHPTOC1.Str.general
1143
SPHHPTOC1:general pickup
Yes
SPHHPTOC1.Str.phsA
1144
SPHHPTOC1:phase A pickup
Yes
SPHHPTOC1.Str.phsB
1145
SPHHPTOC1:phase B pickup
Yes
SPHHPTOC1.Str.phsC
1146
SPHHPTOC1:phase C pickup
Yes
SPHIPTOC1.Op.general
1155
SPHIPTOC1:general trip
SPHIPTOC1.Op.phsA
1156
SPHIPTOC1:phase A trip
SPHIPTOC1.Op.phsB
1157
SPHIPTOC1:phase B trip
SPHIPTOC1.Op.phsC
1158
SPHIPTOC1:phase C trip
SPHIPTOC1.Str.general
1159
SPHIPTOC1:general pickup
Yes
SPHIPTOC1.Str.phsA
1160
SPHIPTOC1:phase A pickup
Yes
No events
61850 Path
IOA
Disabled
Description
Multiplier
Interrogation
Содержание Relion 620 Series
Страница 2: ......
Страница 8: ...Table of contents 1MAC302441 MB A 2 RER620 Point List Manual...
Страница 16: ...Section 1 1MAC302441 MB A Introduction 10 RER620 Point List Manual...
Страница 44: ...Section 2 1MAC302441 MB A IEC 60870 5 101 104 data mappings 38 RER620 Point List Manual...
Страница 58: ...Section 4 1MAC302441 MB A Glossary 52 RER620 Point List Manual...
Страница 59: ......