![ABB Relion 620 Series Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/abb/relion-620-series/relion-620-series_manual_3414585019.webp)
1MAC302441-MB A
Section 2
IEC 60870-5-101/104 data mappings
RER620
13
Point List Manual
VMMXU1.PPV.phsCA.cVal.mag.f
8058
"VA,VB,VC:phase CA amplitude"
Yes
VMMXU1.PPV.phsCA.instCVal.ang.f
8059
"VA,VB,VC:phase CA angle"
Yes
VMMXU2.PhV.phsA.cVal.ang.f
8061
"VA,VB,VC(2):phase A angle"
Yes
VMMXU2.PhV.phsA.cVal.mag.f
8062
"VA,VB,VC(2):phase A amplitude"
Yes
VMMXU2.PhV.phsB.cVal.ang.f
8063
"VA,VB,VC(2):phase B angle"
Yes
VMMXU2.PhV.phsB.cVal.mag.f
8064
"VA,VB,VC(2):phase B amplitude"
Yes
VMMXU2.PhV.phsC.cVal.ang.f
8065
"VA,VB,VC(2):phase C angle"
Yes
VMMXU2.PhV.phsC.cVal.mag.f
8066
"VA,VB,VC(2):phase C amplitude"
Yes
VMMXU2.PPV.phsAB.cVal.mag.f
8067
"VA,VB,VC(2):phase AB amplitude"
Yes
VMMXU2.PPV.phsAB.instCVal.ang.f
8068
"VA,VB,VC(2):phase AB angle"
Yes
VMMXU2.PPV.phsBC.cVal.mag.f
8070
"VA,VB,VC(2):phase BC amplitude"
Yes
VMMXU2.PPV.phsBC.instCVal.ang.f
8071
"VA,VB,VC(2):phase BC angle"
Yes
VMMXU2.PPV.phsCA.cVal.mag.f
8073
"VA,VB,VC(2):phase CA amplitude"
Yes
VMMXU2.PPV.phsCA.instCVal.ang.f
8074
"VA,VB,VC(2):phase CA angle"
Yes
VSMSQI1.SeqV.c1.cVal.mag.f
8076
"V1,V2,V0:amplitude"
Yes
VSMSQI1.SeqV.c1.instCVal.ang.f
8078
"V1,V2,V0:angle"
Yes
VSMSQI1.SeqV.c2.cVal.mag.f
8081
"V1,V2,V0:amplitude"
Yes
VSMSQI1.SeqV.c2.instCVal.ang.f
8083
"V1,V2,V0:angle"
Yes
VSMSQI1.SeqV.c3.cVal.mag.f
8087
"V1,V2,V0:amplitude"
Yes
VSMSQI1.SeqV.c3.instCVal.ang.f
8088
"V1,V2,V0:angle"
Yes
VSMSQI2.SeqV.c1.cVal.mag.f
8091
"V1,V2,V0(2):amplitude"
Yes
VSMSQI2.SeqV.c1.instCVal.ang.f
8093
"V1,V2,V0(2):angle"
Yes
VSMSQI2.SeqV.c2.cVal.mag.f
8097
"V1,V2,V0(2):amplitude"
Yes
VSMSQI2.SeqV.c2.instCVal.ang.f
8098
"V1,V2,V0(2):angle"
Yes
VSMSQI2.SeqV.c3.cVal.mag.f
8102
"V1,V2,V0(2):amplitude"
Yes
VSMSQI2.SeqV.c3.instCVal.ang.f
8103
"V1,V2,V0(2):angle"
Yes
LLN0.Beh.stVal
10000
LLN0:Beh status
Yes
LLN0.LocRem.stVal
10002
LLN0:LocRem status
Yes
LPHD1.NumCmpChg.stVal
10003
LPHD1:NumCmpChg status
Yes
LPHD1.NumPwrUp.stVal
10004
LPHD1:NumPwrUp status
Yes
LPHD1.PhyHealth.stVal
10005
LPHD1:PhyHealth status
Yes
LPHD1.PhyHealth1.stVal
10006
LPHD1:PhyHealth1 status
Yes
LPHD1.PhyHealth2.stVal
10007
LPHD1:PhyHealth2 status
Yes
LPHD1.WacTrg.stVal
10008
LPHD1:WacTrg status
Yes
LPHD1.WrmStr.stVal
10009
LPHD1:WrmStr status
Yes
DNZSRDIR1.OpChrAng.mag.f
10105
32N:OpChrAng magnitude
Yes
DPSRDIR1.OpChrAng.mag.f
10106
32P:OpChrAng magnitude
Yes
DRFLO1.FltLoopX.mag.f
10108
FLO:FltLoopX magnitude
Yes
DRFLO1.FltZ.mag.f
10109
FLO:FltZ magnitude
Yes
NSPTOV2.StrDur.mag.f
10110
47-2:StrDur magnitude
Yes
RDRE1.FltNum.stVal
10111
DFR:FltNum status
Yes
No events 61850 Path
IOA
Disabled
Description
Multiplier Interrogation
Содержание Relion 620 Series
Страница 2: ......
Страница 8: ...Table of contents 1MAC302441 MB A 2 RER620 Point List Manual...
Страница 16: ...Section 1 1MAC302441 MB A Introduction 10 RER620 Point List Manual...
Страница 44: ...Section 2 1MAC302441 MB A IEC 60870 5 101 104 data mappings 38 RER620 Point List Manual...
Страница 58: ...Section 4 1MAC302441 MB A Glossary 52 RER620 Point List Manual...
Страница 59: ......