![ABB Relion 615 series Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_list-manual_3383777029.webp)
Table 3:
Class 2 PRIVATE measurand frames 6 and 7 for REF615 variants FE01,02,03,04
Index
IEC 61850 name
Description
Default scale
Frame No6
Frame No7
Comment
1
LD0.CMMXU1.A.phsA.instCVal.mag
Phase current A
2.4
x
x
2
LD0.CMMXU1.A.phsB.instCVal.mag
Phase current B
2.4
x
x
3
LD0.CMMXU1.A.phsC.instCVal.mag
Phase current C
2.4
x
x
4
LD0.RESCMMXU1.A.res.instCVal.mag
Residual current
2.4
x
x
5
LD0.RESVMMXU1.PhV.res.instCVal.mag
Residual voltage
2.4
x
x
n.a in FE03,04
6
LD0.CSMSQI1.SeqA.c1.instCVal.mag
Positive sequence current
2.4
x
x
7
LD0.CSMSQI1.SeqA.c2.instCVal.mag
Negative sequence current
2.4
x
x
8
LD0.CSMSQI1.SeqA.c3.instCVal.mag
Zero sequence current
2.4
x
x
9
LD0.T1PTTR1.Tmp.mag
Temperature of protected object
1000
x
x
10
LD0.CMSTA1.AvAmps1.mag
Phase current A -average
2.4
x
11
LD0.CMSTA1.AvAmps2.mag
Phase current B -average
2.4
x
12
LD0.CMSTA1.AvAmps3.mag
Phase current C -average
2.4
x
1MRS756712 C