IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
In Use
ASDU
GI
Coding
LD0.PHPTOV3.Op.general
PHPTOV3.OPERATE
Stage 3 Operate[.general]
10=Stage 3 operate
40
98
1
2
0
1
Phase undervoltage protection (3 stages), FE06,07
LD0.PHPTUV3.Str.phsA
-
Stage 3 Start[.phsA]
10=Stage 3 phsA start
41
44
0
2
1
1
LD0.PHPTUV3.Str.phsB
-
Stage 3 Start[.phsB]
10=Stage 3 phsB start
41
45
0
2
1
1
LD0.PHPTUV3.Str.phsC
-
Stage 3 Start[.phsC]
10=Stage 3 phsC start
41
46
0
2
1
1
LD0.PHPTUV2.Str.phsA
-
Stage 2 Start[.phsA]
10=Stage 2 phsA start
41
54
0
2
1
1
LD0.PHPTUV2.Str.phsB
-
Stage 2 Start[.phsB]
10=Stage 2 phsB start
41
55
0
2
1
1
LD0.PHPTUV2.Str.phsC
-
Stage 2 Start[.phsC]
10=Stage 2 phsC start
41
56
0
2
1
1
LD0.PHPTUV1.Str.phsA
-
Stage 1 Start[.phsA]
10=Stage 1 phsA start
41
64
0
2
1
1
LD0.PHPTUV1.Str.phsB
-
Stage 1 Start[.phsB]
10=Stage 1 phsB start
41
65
0
2
1
1
LD0.PHPTUV1.Str.phsC
-
Stage 1 Start[.phsC]
10=Stage 1 phsC start
41
66
0
2
1
1
LD0.PHPTUV1.Str.general
PHPTUV1.START
Stage 1 Start[.general]
10=Stage 1 start
41
84
1
2
1
1
LD0.PHPTUV1.Op.general
PHPTUV1.OPERATE
Stage 1 Operate[.general]
10=Stage 1 operate
41
90
1
2
0
1
LD0.PHPTUV2.Op.general
PHPTUV2.OPERATE
Stage 2 Operate[.general]
10=Stage 2 operate
41
91
1
2
0
1
LD0.PHPTUV2.Str.general
PHPTUV2.START
Stage 2 Start[.general]
10=Stage 2 start
41
94
1
2
1
1
LD0.PHPTUV3.Str.general
PHPTUV3.START
Stage 3 Start[.general]
10=Stage 3 start
41
96
1
2
1
1
LD0.PHPTUV3.Op.general
PHPTUV3.OPERATE
Stage 3 Operate[.general]
10=Stage 3 operate
41
98
1
2
0
1
Positive sequence undervoltage protection (1 stage), FE06,07
LD0.PSPTUV1.Str.phsA
-
Start[.phsA]
10=phsA start
42
64
0
2
1
1
LD0.PSPTUV1.Str.phsB
-
Start[.phsB]
10=phsB start
42
65
0
2
1
1
LD0.PSPTUV1.Str.phsC
-
Start[.phsC]
10=phsC start
42
66
0
2
1
1
LD0.PSPTUV1.Str.general
PSPTUV1.START
Start[.general]
10=Start
42
84
1
2
1
1
LD0.PSPTUV1.Op.general
PSPTUV1.OPERATE
Operate[.general]
10=Operate
42
90
1
2
0
1
Negative sequence overvoltage protection (1 stage), FE06,07
LD0.NSPTOV1.Str.phsA
-
Start[.phsA]
10=phsA start
43
64
0
2
1
1
LD0.NSPTOV1.Str.phsB
-
Start[.phsB]
10=phsB start
43
65
0
2
1
1
LD0.NSPTOV1.Str.phsC
-
Start[.phsC]
10=phsC start
43
66
0
2
1
1
LD0.NSPTOV1.Str.general
NSPTOV1.START
Start[.general]
10=Start
43
84
1
2
1
1
LD0.NSPTOV1.Op.general
NSPTOV1.OPERATE
Operate[.general]
10=Operate
43
90
1
2
0
1
Residual overvoltage protection (3 stages), FE06,07
LD0.ROVPTOV1.Str.general
ROVPTOV1.START
Stage 1 Start
10=Stage 1 start
44
84
1
2
1
1
LD0.ROVPTOV1.Op.general
ROVPTOV1.OPERATE
Stage 1 Operate
10=Stage 1 operate
44
90
1
2
0
1
LD0.ROVPTOV2.Op.general
ROVPTOV2.OPERATE
Stage 2 Operate
10=Stage 2 operate
44
91
1
2
0
1
LD0.ROVPTOV2.Str.general
ROVPTOV2.START
Stage 2 Start
10=Stage 2 start
44
94
1
2
1
1
LD0.ROVPTOV3.Str.general
ROVPTOV3.START
Stage 3 Start
10=Stage 3 start
44
96
1
2
1
1
LD0.ROVPTOV3.Op.general
ROVPTOV3.OPERATE
Stage 3 Operate
10=Stage 3 operate
44
98
1
2
0
1
Physical binary I/O signals
LD0.XGGIO130.Ind1.stVal
-
X130-Input 1
10=ON, 01=OFF
50
1
0
1
1
1
LD0.XGGIO130.Ind2.stVal
-
X130-Input 2
10=ON, 01=OFF
50
2
0
1
1
1
Table continues on next page
1MRS756712 C
Section 2
IEC 60870-5-103 data mappings
REF615
17
Point List Manual