IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
In Use
ASDU
GI
Coding
Directional earth-fault protection (3 stages), FE01,02,05,06, 07
LD0.DEFLPTOC1.Str.general
DEFLPDEF1.START
Low(1) stage start
10=Low(1) stage start
163
84
1
2
1
1
LD0.DEFLPTOC1.Op.general
DEFLPDEF1.OPERATE
Low(1) stage operate
10=Low(1) stage operate
163
90
1
2
0
1
LD0.DEFLPTOC2.Op.general
DEFLPDEF2.OPERATE
Low(2) stage operate
10=Low(2) stage operate
163
91
1
2
0
1
LD0.DEFLPTOC2.Str.general
DEFLPDEF2.START
Low(2) stage start
10=Low(2) stage start
163
94
1
2
1
1
LD0.DEFHPTOC1.Str.general
DEFHPDEF1.START
High stage start
10=High stage start
163
96
1
2
1
1
LD0.DEFHPTOC1.Op.general
DEFHPDEF1.OPERATE
High stage operate
10=High stage operate
163
98
1
2
0
1
Three-phase inrush detection, all variants
LD0.INRPHAR1.Str.phsA
-
Start[.phsA]
10=Start phsA
167
64
0
2
1
1
LD0.INRPHAR1.Str.phsB
-
Start[.phsB]
10=Start phsB
167
65
0
2
1
1
LD0.INRPHAR1.Str.phsC
-
Start[.phsC]
10=Start phsC
167
66
0
2
1
1
LD0.INRPHAR1.Str.general
-
Start[.general]
10=Start general
167
84
1
2
1
1
Thermal overload protection, all variants
LD0.T1PTTR1.Str.general
T1PTTR1.START
Start
10=Start
168
84
1
2
1
1
LD0.T1PTTR1.AlmThm.general
T1PTTR1.ALARM
Thermal alarm
10=Thermal alarm
168
85
1
2
1
1
LD0.T1PTTR1.Op.general
T1PTTR1.OPERATE
Operate
10=Operate
168
90
1
2
0
1
Auto-reclosing, optional in all variants
LD0.DARREC1.RsRec.ctlVal
-
AR reset
10=Reset
169
19
1
20
0
1
LD0.DARREC1.RsCnt.ctlVal
-
AR counters reset
10=Reset
169
20
1
20
0
1
LD0.DARREC1.PrgRec1.stVal
DARREC1.INPRO_1
AR in progress 1st reclose
10=In progress
169
101
1
2
0
1
LD0.DARREC1.PrgRec2.stVal
DARREC1.INPRO_2
AR in progress 2nd reclose
10=In progress
169
102
1
2
0
1
LD0.DARREC1.PrgRec3.stVal
DARREC1.INPRO_3
AR in progress 3rd reclose
10=In progress
169
103
1
2
0
1
LD0.DARREC1.PrgRec4.stVal
DARREC1.INPRO_4
AR in progress 4th reclose
10=In progress
169
104
1
2
0
1
LD0.DARREC1.PrgRec5.stVal
DARREC1.INPRO_5
AR in progress 5th reclose
10=In progress
169
105
1
2
0
1
LD0.DARREC1.PrgRec.stVal
DARREC1.INPRO
AR in progress
10=In progress
169
120
1
2
0
1
LD0.DARREC1.CBManCls.stVal
DARREC1.MAN_CB_CL
CB manually closed
10=CB manually closed
169
159
1
2
0
1
LD0.DARREC1.LO.stVal
DARREC1.LOCKED
Lockout status
10=Lockout
169
164
1
2
0
1
LD0.DARREC1.UnsRec.stVal
DARREC1.UNSUC_RECL
Unsuccessful reclose status
10=Unsuccessful reclose
169
170
1
2
0
1
LD0.DARREC1.InBlkThm.stVal
-
Thermal block (status)
10=Thermal block
169
171
1
2
0
1
LD0.DARREC1.RdyRec.stVal
DARREC1.READY
Ready reclose status
10=Reclose ready
169
172
1
2
0
1
LD0.DARREC1.ActRec.stVal
DARREC1.ACTIVE
Active reclose status
10=Reclose active
169
173
1
2
0
1
LD0.DARREC1.PrgDsr.stVal
DARREC1.DISCR_INPRO
Discrimination time in progress
10=Discrimination time in progress
169
174
1
2
0
1
LD0.DARREC1.PrgCutOut.stVal
DARREC1.CUTOUT_INPR O
Cutout time in progress
10=Cutout time in progress
169
175
1
2
0
1
LD0.DARREC1.FrqOpAlm.stVal
DARREC1.FRQ_OP_ALM
Frequent operation counter alarm
10=Frequent operation alarm
169
176
1
2
0
1
LD0.DARREC1.RclTmStr.stVal
-
Reclaim time started
10=Reclaim time started
169
177
1
2
0
1
LD0.DARREC1.ProCrd.stVal
-
Protection coordination
10=Protection coordination
169
178
1
2
0
1
LD0.DARREC1.Op.general
DARREC1.CLOSE_CB
Operate (close command to XCBR)
10=Close command to CB
169
179
1
2
0
1
Table continues on next page
Section 2
1MRS756712 C
IEC 60870-5-103 data mappings
20
REF615
Point List Manual
Содержание Relion 615 series
Страница 1: ...Relion 615 series Feeder Protection and Control REF615 IEC 60870 5 103 Point List Manual...
Страница 2: ......
Страница 16: ...10...
Страница 38: ...32...
Страница 39: ...33...