Table 2:
Indications and controls
IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
In Use
ASDU
GI
Coding
Device function type - standard, all variants
LD0.DARREC1.AROn.stVal
-
Autorecloser state
10=AR On, 01=AR Off
0
16
1
1
1
1
LD0.LLN0.LEDRs1.ctlVal
-
LED reset
10=Reset
indications
and
alarm
LEDs
0
19
1
20
0
1
LD0.LLN0.Beh.stVal (Test mode)
-
Test mode
10=Test mode ON, 01=Test mode OFF
0
21
1
1
1
1
LD0.I3CGGIO1.ActSG.ctlVal
-
Parameter setting group 1
10=Setting group 1 in use
0
23
1
1,20
1
1
LD0.I3CGGIO1.ActSG.ctlVal
-
Parameter setting group 2
10=Setting group 2 in use
0
24
1
1,20
1
1
LD0.I3CGGIO1.ActSG.ctlVal
-
Parameter setting group 3
10=Setting group 3 in use
0
25
1
1,20
1
1
LD0.I3CGGIO1.ActSG.ctlVal
-
Parameter setting group 4
10=Setting group 4 in use
0
26
1
1,20
1
1
LD0.I3CGGIO1.ActSG.ctlVal
-
Parameter setting group 5
10=Setting group 5 in use
0
27
1
1,20
1
1
LD0.I3CGGIO1.ActSG.ctlVal
-
Parameter setting group 6
10=Setting group 6 in use
0
28
1
1,20
1
1
LD0.TCSSCBR1.CirAlm.stVal
TCSSCBR1.ALARM
Trip circuit 1 alarm
10=TCS1 alarm
0
36
1
1
1
1
LD0.LEDPTRC1.Op.general
-
Global operate
10=Operate (LEDPTRC)
0
68
1
2
0
1
LD0.LEDPTRC1.Str.general
-
Global start
10=Start (LEDPTRC)
0
84
1
2
1
1
LD0.DARREC1.SucRec.stVal
DARREC1.SUC_RECL
Successful reclose status
10=Successful reclose
0
128
1
1
0
1
LD0.DARREC1.InInhRec.stVal
-
Inhibit reclose (status)
10=Reclose inhibit
0
130
1
1
1
1
Device function type - private, all variants
LD0.TRPPTRC1.Op.general
-
TRPTRC1 input signal
10=Input signal ON
10
1
1
2
0
1
LD0.TRPPTRC1.Tr.general
-
TRPTRC1 trip output signal
10=Trip output signal ON
10
2
1
2
0
1
LD0.TRPPTRC2.Op.general
-
TRPTRC2 input signal
10=Input signal ON
10
3
1
2
0
1
LD0.TRPPTRC2.Tr.general
-
TRPTRC2 trip output signal
10=Trip output signal ON
10
4
1
2
0
1
CTRL.LLN0.Loc.stVal
-
Local/Remote state
10=Local, 01=Remote
10
10
1
1
1
1
CTRL.LLN0.LocRem.Station
-
Station state
10=Station ON, 01=OFF
10
11
1
1
1
1
LD0.LLN0.RecRs.ctlVal
-
Reset all data
10=Reset all data
10
19
1
20
0
1
LD0.LLN0.LEDRs2.ctlVal
-
Reset alarm LEDs
10=Reset alarm LEDs only
10
21
1
20
0
1
LD0.TCSSCBR2.CirAlm.stVal
TCSSCBR2.ALARM
Trip circuit 2 alarm
10=TCS2 alarm
10
36
1
1
1
1
DR.RDRE1.RcdTrg.ctlVal
-
Trig DR recording
10=External DR trig
10
41
1
20
0
1
DR.RDRE1.MemClr.ctlVal
-
Clear DR memory
10=Clear memory
10
42
1
20
0
1
LD0.CMSTA1.RecRs.ctlVal
-
Reset CMMXU1 max.demands
10=Reset max values
10
45
1
20
0
1
Multipurpose inputs (all variants)
LD0.MVGAPC1.Q1.stVal
-
MVGAPC1 input 1 signal
10=Input ON, 01=OFF
11
1
0
1
1
1
LD0.MVGAPC1.Q2.stVal
-
MVGAPC1 input 2 signal
10=Input ON, 01=OFF
11
2
0
1
1
1
LD0.MVGAPC1.Q3.stVal
-
MVGAPC1 input 3 signal
10=Input ON, 01=OFF
11
3
0
1
1
1
LD0.MVGAPC1.Q4.stVal
-
MVGAPC1 input 4 signal
10=Input ON, 01=OFF
11
4
0
1
1
1
LD0.MVGAPC1.Q5.stVal
-
MVGAPC1 input 5 signal
10=Input ON, 01=OFF
11
5
0
1
1
1
LD0.MVGAPC1.Q6.stVal
-
MVGAPC1 input 6 signal
10=Input ON, 01=OFF
11
6
0
1
1
1
LD0.MVGAPC1.Q7.stVal
-
MVGAPC1 input 7 signal
10=Input ON, 01=OFF
11
7
0
1
1
1
LD0.MVGAPC1.Q8.stVal
-
MVGAPC1 input 8 signal
10=Input ON, 01=OFF
11
8
0
1
1
1
Table continues on next page
Section 2
1MRS756712 C
IEC 60870-5-103 data mappings
14
REF615
Point List Manual