IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
In Use
ASDU
GI
Coding
LD0.DARREC1.OpOpn.general
DARREC1.OPEN_CB
Operate (open command to XCBR)
10=Open command to CB
169
180
1
2
0
1
LD0.DARREC1.UnsCBCls.stVal
DARREC1.UNSUC_CB
Unsuccessful CB closing status
10=Unsuccessful CB closing
169
181
1
2
0
1
LD0.DARREC1.WtMstr.stVal
DARREC1.CMD_WAIT
Master signal to follower
10=Master signal to follower
169
182
1
2
0
1
Phase currents limit supervision, all variants
LD0.CMMXU1.HiAlm.stVal
CMMXU1.HIGH_ALARM
High alarm
10=High alarm
210
1
0
1
1
1
LD0.CMMXU1.HiWrn.stVal
CMMXU1.HIGH_WARN
High warning
10=High warning
210
2
0
1
1
1
LD0.CMMXU1.LoWrn.stVal
CMMXU1.LOW_WARN
Low warning
10=Low warning
210
3
0
1
1
1
LD0.CMMXU1.LoAlm.stVal
CMMXU1.LOW_ALARM
Low alarm
10=Low alarm
210
4
0
1
1
1
Residual current limit supervision, all variants
LD0.RESCMMXU1.HiAlm.stVal
RESCMMXU1.HIGH_ALAR M
High alarm
10=High alarm
210
11
0
1
1
1
LD0.RESCMMXU1.HiWrn.stVal
RESCMMXU1.HIGH_WAR N
High warning
10=High warning
210
12
0
1
1
1
Phase-to-phase voltage limit supervision, FE05,06,07
LD0.VMMXU1.HiAlm.stVal
VMMXU1.HIGH_ALARM
High alarm
10=High alarm
211
1
0
1
1
1
LD0.VMMXU1.HiWrn.stVal
VMMXU1.HIGH_WARN
High warning
10=High warning
211
2
0
1
1
1
LD0.VMMXU1.LoWrn.stVal
VMMXU1.LOW_WARN
Low warning
10=Low warning
211
3
0
1
1
1
LD0.VMMXU1.LoAlm.stVal
VMMXU1.LOW_ALARM
Low alarm
10=Low alarm
211
4
0
1
1
1
Residual voltage limit supervision, FE01,02,05,06,07
LD0.RESVMMXU1.HiAlm.stVal
RESVMMXU1.HIGH_ALAR M
High alarm
10=High alarm
211
11
0
1
1
1
LD0.RESVMMXU1.HiWrn.stVal
RESVMMXU1.HIGH_WAR N
High warning
10=High warning
211
12
0
1
1
1
Circuit breaker position and failure protection, all variants
CTRL.CBCILO1.EnaOpn.stVal
CBXCBR1.ENA_OPEN
CB open enabled
10=Open enabled
240
21
1
1
1
1
CTRL.CBCILO1.EnaCls.stVal
CBXCBR1.ENA_CLOSE
CB close enabled
10=Close enabled
240
22
1
1
1
1
CTRL.CBXCBR1.BlkOpn.stVal
CBXCBR1.BLK_OPEN
CB open blocked
10=Open blocked
240
23
1
1
1
1
CTRL.CBXCBR1.BlkCls.stVal
CBXCBR1.BLK_CLOSE
CB close blocked
10=Close blocked
240
24
1
1
1
1
CTRL.CCBRBRF1.Str.general
CCBRBRF1.CB_FAULT_AL
Start, timer running
10=Start,timer running
240
101
0
2
1
1
CTRL.CCBRBRF1.OpEx.general
CCBRBRF1.TRBU
Failure, external trip
10=Failure,external trip
240
102
0
2
0
1
CTRL.CCBRBRF1.OpIn.general
CCBRBRF1.TRRET
Operate, internal retrip
10=Operate, internal re-trip
240
103
0
2
0
1
CTRL.CBCSWI1.Pos.stVal
CBXCBR1.POSITION
Circuit breaker position
10=Close;01=Open;00=Intermediate; 11=Error
240
160
1
1,20
1
2
Circuit breaker condition monitoring, FE02,04,05,06,07
LD0.SSCBR1.RsAccAPwr.ctlVal
SSCBR1.RST_IPOW
Reset accumulation energy
10=Reset
242
19
1
20
0
1
LD0.SSCBR1.RsCBWear.ctlVal
SSCBR1.RST_CB_WEAR
Reset CB remaining life and op.counters
10=Reset
242
20
1
20
0
1
LD0.SSCBR1.RsTrvTm.ctlVal
SSCBR1.RST_TRV_T
Reset CB travelling time alarm
10=Reset
242
21
1
20
0
1
LD0.SSCBR1.RsSprChaTm.ctlVal
SSCBR1.RST_SPR_T
Reset CB spring charge time alarm
10=Reset
242
22
1
20
0
1
LD0.SSCBR1.OpnAlm.stVal
SSCBR1.TRV_T_OP_ALM
Open travel time exceeded
10=Open travel time alarm
242
101
0
1
0
1
Table continues on next page
1MRS756712 C
Section 2
IEC 60870-5-103 data mappings
REF615
21
Point List Manual