98
Line differential protection (DIFL)
&KDSWHU
9HULI\LQJVHWWLQJVE\VHFRQGDU\
LQMHFWLRQ
/LQHGLIIHUHQWLDOSURWHFWLRQ',)/
When testing the differential protection it is important to be aware of that actions taken
locally may cause operation of the terminal in the remote end.
At commissioning and after changes in the current circuits, the trip signals at
ERWK
ter-
minals must be blocked permanently
EHIRUH
the dc supply is connected. This precaution
is taken to avoid unwanted local and remote trip in case of error in the current circuits.
The blocking can
QRW
be done by the COMBITEST test switch. It has to be made on the
station side of the test switch because the test switch disconnects the current inputs to
the terminal and thus causes current unbalance in the differential circuit. This will cause
the remote end terminal to trip if not blocked. The blocking of the trip signal must be
maintained, until the test has been performed at both terminals.
Any work in any of the terminals, such as injecting current or to short-circuit the current
during load transfer on the line, will result in a local and
5(027(
end trip.
When the current balance is disturbed by any action, the protections at both line ends
must be blocked.
Before performing any work in the current circuit to the line differential protection, the
7HVW0RGH
must be activated and saved. The protection will
QRW
enter into test mode
without saving the command.
When the protection is equipped with a COMBITEST test switch, inserting the test han-
dle will automatically force the protection into test mode. This function is also achieved
by activating the
7HVW
digital input. The test mode command must be saved to be acti-
vated.
It is sufficient if one of the terminals is set in test mode. The trip function is blocked
automatically at both line ends, when one of the protection terminals is in test mode.
Thus the protection can be tested without any manual actions in the remote station.
Testing can be performed only when the terminals communicate with each other and if
RQHDQGRQHRQO\
of the terminals is in test mode.
To activate the local trip relays during the test for operating time measurement, the
blocking of the trip is overridden in the terminal in test mode by the command “Local
trip”.
For a complete test of the protection, the tests must be repeated at both terminals.
Содержание REL 531
Страница 16: ...10 Note signs KDSWHU 6DIHW LQIRUPDWLRQ ...
Страница 44: ...38 Checking the binary I O circuits KDSWHU KHFNLQJ WKH H WHUQDO FLUFXLWU ...
Страница 52: ...46 Checking the self supervision signals KDSWHU QHUJLVLQJ WKH WHUPLQDO ...
Страница 132: ...126 Two step time delayed phase overcurrent protection TOC2 KDSWHU 9HULI LQJ VHWWLQJV E VHFRQGDU LQMHFWLRQ ...
Страница 136: ...130 Testing the interaction of the distance protection KDSWHU 9HULI LQJ WKH LQWHUQDO FRQILJXUDWLRQ ...
Страница 140: ...134 Testing the interaction of the distance protection KDSWHU 7HVWLQJ WKH SURWHFWLRQ V VWHP ...