IGenZeroDb: Minimum level of current in % of IBase, used as indication of zero current (zero
point clamping). If measured value is below
IGenZeroDb calculated S, P, Q and PF will be zero.
UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y% of Ur, where
Y is equal to 5, 30 or 100.
IAmpCompY: Amplitude compensation to calibrate current measurements at Y% of Ir, where Y
is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir, where Y is
equal to 5, 30 or 100.
The following general settings can be set for the Phase current measurement (CMMXU).
IAmpCompY: Amplitude compensation to calibrate current measurements at Y% of Ir, where Y
is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir, where Y is
equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase voltage measurement
(VMMXU).
UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y% of Ur, where
Y is equal to 5, 30 or 100.
UAngCompY: Angle compensation to calibrate angle measurements at Y% of Ur, where Y is
equal to 5, 30 or 100.
The following general settings can be set for all monitored quantities included in the
functions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X in setting names below
equals S, P, Q, PF, U, I, F, IL1-3, UL1-3UL12-31, I1, I2, 3I0, U1, U2 or 3U0.
Xmin: Minimum value for analog signal X set directly in applicable measuring unit. This forms
the minimum limit of the range.
Xmax: Maximum value for analog signal X. This forms the maximum limit of the range.
XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.
Observe the related zero point clamping settings in Setting group N for CVMMXN
(
UGenZeroDb and IGenZeroDb). If measured value is below UGenZeroDb and/or IGenZeroDb
calculated S, P, Q and PF will be zero and these settings will override
XZeroDb.
XRepTyp: Reporting type. Cyclic (Cyclic), amplitude deadband (Dead band), integral deadband
(
Int deadband) or Deadband and xx se cyclic (xx: 5 sec, 30 sec, 1 min). The reporting interval is
controlled by the parameter
XDbRepInt.
XDbRepInt: This setting handles all the reporting types. If setting is deadband in XRepTyp,
XDbRepInt defines the deadband in m% of the measuring range. For cyclic reporting type
(
XRepTyp : cyclic), the setting value reporting interval is in seconds. Amplitude deadband is the
setting value in m% of measuring range. Integral deadband setting is the integral area, that is,
measured value in m% of measuring range multiplied by the time between two measured
values.
XHiHiLim: High-high limit. Set as % of YBase (Y is SBase for S,P,Q UBase for Voltage
measurement and
IBase for current measurement).
XHiLim: High limit. Set as % of YBase (Y is SBase for S,P,Q UBase for Voltage measurement and
IBase for current measurement).
Section 14
1MRK 505 370-UEN D
Monitoring
356
Busbar protection REB670
Application manual
Содержание REB670 Series
Страница 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 64: ...58 ...
Страница 226: ...220 ...
Страница 244: ...238 ...
Страница 358: ...352 ...
Страница 392: ...386 ...
Страница 398: ...392 ...
Страница 436: ...430 ...
Страница 454: ...448 ...
Страница 466: ...460 ...
Страница 474: ...468 ...
Страница 475: ...469 ...