QB7OPTR (bay 1)
BB_DC_OP
VP_BB_DC
EXDU_BB
en04000510.vsd
&
&
&
QB7OPTR (bay n)
. . .
. . .
. . .
VPQB7TR (bay 1)
VPQB7TR (bay n)
EXDU_BB (bay 1)
EXDU_BB (bay n)
. . .
. . .
. . .
. . .
. . .
. . .
IEC04000510 V1 EN-US
Figure 181: Signals from bypass busbar to busbar earthing switch
12.4.7.3
Signals in double-breaker arrangement
M15053-83 v4
The busbar earthing switch is only allowed to operate if all disconnectors of the bus section
are open.
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
BB_ES
DB_BUS
(WA1)A1
(WA2)B1
B2
A2
en04000511.vsd
DB_BUS
IEC04000511 V1 EN-US
Figure 182: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
All disconnectors of this part of the busbar are open.
VP_BB_DC
The switch status of all disconnectors on this part of the busbar are valid.
EXDU_BB
No transmission error from any bay that contains the above information.
These signals from each double-breaker bay (DB_BUS) are needed:
Signal
QB1OPTR
QB1 is open.
QB2OPTR
QB2 is open.
VPQB1TR
The switch status of QB1 is valid.
VPQB2TR
The switch status of QB2 is valid.
EXDU_DB
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module (A1A2_DC)
Section 12
1MRK 505 370-UEN D
Control
326
Busbar protection REB670
Application manual
Содержание REB670 Series
Страница 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 64: ...58 ...
Страница 226: ...220 ...
Страница 244: ...238 ...
Страница 358: ...352 ...
Страница 392: ...386 ...
Страница 398: ...392 ...
Страница 436: ...430 ...
Страница 454: ...448 ...
Страница 466: ...460 ...
Страница 474: ...468 ...
Страница 475: ...469 ...