Setting
Short Description
Selected
value
Comments
IAngComp5
Angle calibration for current at
5% of Ir
0.00
IAngComp30
Angle pre-calibration for
current at 30% of Ir
0.00
IAngComp100
Angle pre-calibration for
current at 100% of Ir
0.00
Measurement function application for a power transformer
SEMOD54481-61 v9
Single line diagram for this application is given in figure
110kV Busbar
200/1
35 / 0,1
kV
35kV Busbar
500/5
P
Q
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
U
L1L2
IEC09000040-1-en.vsd
IED
IEC09000040-1-EN V1 EN-US
Figure 197: Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure
do the following:
Section 14
1MRK 505 370-UEN D
Monitoring
360
Busbar protection REB670
Application manual