EnaAbs: This setting is used to select the comparison type between signed and absolute
values.
•
Absolute: Comparison is performed on absolute values of input and reference values
•
Signed: Comparison is performed on signed values of input and reference values.
RefSource: This setting is used to select the reference source between input and setting for
comparison.
•
Input REF: The function will take reference value from input REF
•
Set Value: The function will take reference value from setting SetValue
SetValue: This setting is used to set the reference value for comparison when setting
RefSource is selected as SetValue.
13.13.4
Setting example
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
For absolute comparison between inputs:
Set the
EnaAbs = Absolute
Set the
RefSource = Input REF
Similarly for Signed comparison between inputs
Set the
EnaAbs = Signed
Set the
RefSource =Input REF
For absolute comparison between input and setting
Set the
EnaAbs = Absolute
Set the
RefSource = Set Value
SetValue shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the
EnaAbs = Signed
Set the
RefSource = Set Value
SetValue shall be set between -2000000000 to 2000000000
13.14
Comparator for real inputs - REALCOMP
13.14.1
Identification
GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparator for real inputs
REALCOMP
Real<=>
1MRK 505 370-UEN D
Section 13
Logic
Busbar protection REB670
349
Application manual
Содержание REB670 Series
Страница 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 64: ...58 ...
Страница 226: ...220 ...
Страница 244: ...238 ...
Страница 358: ...352 ...
Страница 392: ...386 ...
Страница 398: ...392 ...
Страница 436: ...430 ...
Страница 454: ...448 ...
Страница 466: ...460 ...
Страница 474: ...468 ...
Страница 475: ...469 ...