Introduction to the manual
3ADW0005Q964 E-Stop cat.1 without opening mains contactor en b
Quick reference guide for implementing a safety system
Task
Select the appropriate functional safety standard for the implementation: EN ISO 13849-1,
EN/IEC 62061, IEC 61511 or other
If you select EN/IEC 62061 or IEC 61511, make a safety plan. See EN/IEC 62061.
Assess safety: analyze and evaluate risks (estimate SIL/PL) and define risk reduction
strategies.
Define the safety requirements
Design the safety system. The part of the design made by ABB is described in chapter
Option description and instructions
on page 8.
If you made any changes to the delivered safety system, verify the achieved SIL/PL with, for
example, FSDT-01 Functional safety design tool or similar. See
Functional safety design tool
user’s manual
(3AXD10000102417 [English]).
Connect the wiring. See section
Wiring
on page 14.
Set the parameters. See section
Parameter settings
on page 11.
Validate that the implemented system meets the safety requirements:
−
Do the acceptance test. See section
Start-up and acceptance test
on page 15
Write the necessary documentation.