Additional information
Task
Use a vacuum cleaner to clean the floor, doors
and interior beams.
See MV transformer manual.
Use a pressurized air to clean the general dust in
the MV transformer surface and locations with
excessive dust.
Use pressurized air to clean locations with excess-
ive dust, including busbar connections.
Clean the surface of the MV transformer with a
duster or compressed air.
Clean the insulators of the MV transformer
Cleaning the air filters
Clean the air filters by blowing compressed air
from the inside to the outside through the filter
until the dust comes off.
Loosen and remove the screws on the filter frame.
Remove the plastic clips and then, remove the
grid.
Clean the grill interior with a vacuum cleaner.
Install the filter support frames and tighten the
screws.
Cleaning the fans
Prevent the circuit breaker from turning on acci-
dentally.
Turn OFF/OPEN the circuit breaker for fan.
Measure to make sure that it is not energized.
Disconnect the supply and signal cabling.
Use compressed air to clean the fans.
Cleaning the free area
If necessary, use a duster or pressurized air to
clean locations you cannot reach with the vacuum
cleaner.
Use a vacuum cleaner to clean the floor, doors
and interior.
Cleaning the MV switchgear area
If necessary, use a duster or pressurized air to
clean locations you cannot reach with the vacuum
cleaner.
Use a vacuum cleaner to clean the floor, doors
and interior metal beams.
Maintenance 59
Содержание PVS-175 Series
Страница 1: ... ABB SOLAR INVERTERS PVS 175 medium voltage station Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 14: ...14 ...
Страница 26: ...26 ...
Страница 32: ...32 ...
Страница 40: ...6 Apply a layer of sealant around the hood border 40 Mechanical installation ...
Страница 48: ...48 ...
Страница 54: ...54 ...
Страница 60: ...Replacing component 1 Loosen and remove the external screws of the ventilation grille 60 Maintenance ...
Страница 68: ...68 ...
Страница 70: ......