Type designation key
The type designation describes the composition of the unit. The type designation is visible
on the type designation label which is attached to the unit. The complete type designation
is divided into sub codes:
•
The first 1…18 digits form the basic code which describes the basic construction of the
unit. The fields in the basic code are separated by hyphens.
•
The option codes follow the basic code. Each option code starts with an identifying letter
(common for the whole product series), followed by descriptive digits. The option codes
are separated by plus signs.
The following table describes the fields of the basic code and the option code. Refer to the
items of figure in
Description
Item
MVS = Station type
E
Power rating
F
XXXXkVA
See chapter
LV voltage
G
-Y = 800 V
Option (plus) codes for additional upgrades
H
■
MVS optional codes
Description
Name
Code
MV dry transformer
Standard losses dry transformer is replaced with eco losses dry
transformer
Dry transformer ECO
losses
+TRECO
Standard losses dry transformer 22kV is replaced with dry
transformer 33kV
Dry transformer
36kV
+TR36kV
Standard losses dry transformer 60 Hz is replaced with dry
transformer 50 Hz
Dry transformer
50Hz
+TR50Hz
Auxiliary service board
Standard 10 KVA auxiliary service transformer is upgraded to a 20 KVA
400/230 V auxiliary service transformer
Auxiliary transformer
power rating
+ATR20
Standard 10 KVA auxiliary service transformer is upgraded to a 30 KVA
400/230 V auxiliary service transformer
Auxiliary transformer
power rating
+ATR30
An additional auxiliary monophase auxiliary service transformer of 3kVA
is installed to provide customer with specified voltage
level and frequency
Additional mono-
phase auxiliary
transformer power
rating
+ATR3
Standard surge protection device Type II is replaced with dtandard
durge protection device Type I + II. Only applicable for
PVS-175 stations
AC standard surge
protection device
Type I + II 800 V
+SPD412
Standard surge protection device Type II is replaced with standard
surge protection device type I + II. Only applicable
for PVS-100/120 stations
AC standard surge
protection device
Type I + II 400 V
+SPD412
24 Hardware description
Содержание PVS-175 Series
Страница 1: ... ABB SOLAR INVERTERS PVS 175 medium voltage station Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 14: ...14 ...
Страница 26: ...26 ...
Страница 32: ...32 ...
Страница 40: ...6 Apply a layer of sealant around the hood border 40 Mechanical installation ...
Страница 48: ...48 ...
Страница 54: ...54 ...
Страница 60: ...Replacing component 1 Loosen and remove the external screws of the ventilation grille 60 Maintenance ...
Страница 68: ...68 ...
Страница 70: ......