Electrical connections
42 - EN
FEX300, FEX500
CI/FEX300/FEX500-EN
5.6.2 Devices with PROFIBUS PA or FOUNDATION fieldbus
G01032
A
51 52 81 82
4
1
4
2
L
N
1
+
2
-
M1 M2
D
1
D
2 3 2S E2 E1 1S
M1 M2
D
1
D
2 3 2S E2 E1 1S
SE
B
{
{
{
{
{
2
3
4
5
1
PE
7
8
9
10 11
12 13
6
6
<
50
m
(200
m
)
<
16
4 ft
(656
ft
)
SE
+
-
97 98
PA
+
PA
-
FF+ FF-
Fig. 39
A
Transmitter
B
Flowmeter sensor
1
Power supply
See name plate
2
Digital communication (terminal 97 / 98)
• PROFIBUS PA in acc. with IEC 61158-2 (PA+ / PA-)
U = 9 ... 32 v, I = 10 mA (normal operation), I = 13 mA (in the event of an error / FDE)
Bus connection with integrated protection against polarity reversal
The bus address can be set via the DIP switches in the device (with dual-compartment transmitter housing only), the transmitter
display or the fieldbus.
or
• FOUNDATION fieldbus in acc. with IEC 61158-2 (FF+ / FF-)
U = 9 ... 32 v, I = 10 mA (normal operation), I = 13 mA (in the event of an error / FDE)
Bus connection with integrated protection against polarity reversal
3
Not
assigned
4
Not
assigned
5
Digital output DO2 (terminals 41 / 42) (pulse output or digital output)
Function can be configured locally as "Pulse Output" or "Digital Output" using software.
Factory setting is "Digital Output", flow direction signaling.
The output is always a "passive" output (optocoupler).
Data for the optocoupler: U
max
= 30 V, I
max
= 220 mA, f
max
≤
5250 Hz
6
Functional ground
7
Brown
8
Red
9
Orange
10
Yellow
11
Green
12
Blue
13
Violet
Important (Note)
For detailed information about grounding the transmitter and the flowmeter sensor, please refer to the section titled
"Installation / grounding".