Commissioning
CI/FEX300/FEX500-EN
FEX300, FEX500
EN - 51
6.4.1 Transmitter with dual-compartment housing
G00679-02
5
4
„A“
„
B
“
1
2 3
3
6
7
Fig. 50
A Integral mount design
B Remote mount design
1
Housing cover
2
Transmitter plug-in module
3
Fixing screws
4
Backplane (in the transmitter housing)
5
Jumper (BR901) for active / passive current output
6
Jumper (BR903) for integral / remote mount design
7
Jumper (BR902) for hardware write protection
Important (Note)
The backplane is mounted in the transmitter housing (not the transmitter plug-in module).
Configure the outputs as follows:
1. Switch off power supply.
2. Open the housing cover.
3. Remove the mounting screws for the transmitter electronics unit
4. Pull out the transmitter electronics unit
5.
Set jumpers on backplane in accordance with the following table.
Jumper
Number
Function
BR901
active
Current output 31 / 32 active
passive
Current output 31 / 32 passive
BR902
Read only
Hardware write protection active
BR903
integral
Transmitter with integral mount design
remote
Transmitter with remote mount design
6. Reinstall the transmitter electronic unit in reverse order