6.3.2
AS400 Dry Contact card
Alarm indication is possible through the AS400 potential free (dry contact) card. The following is the pin
assignment and description of DB-9 connector in AS400 card.
Figure 27: RS-232 Communication Port (DB-9 Connector)
Pin Number Description
I/O
1
UPS Fail
Output
2
Summary Alarm
Output
3
GND
Input
4
Remote Shutdown Input
5
Common
Input
6
Bypass
Output
7
Battery Low
Output
8
UPS ON
Output
9
Line Loss
Output
Table 7: RS- 232 Port Pin Assignment
For more information on the potential free cards, see the AS400 User's Manual.
6.3.3
Monitoring Software
ABB UPS can be monitored through a software that allows the user to monitor the UPS. The software
provides a remote and safe shutdown for multi-client systems in case of absence of power in the output
of the UPS. Instructions on how to install the software are provided with the network management
cards.