To modify a parameter, press
for less than 1 second and scroll up or down. To confirm the selection
press this same button
for more than 1 second.
Figure 24: Setting menu tree
If the password is enabled, the user must enter the password
USER
by pressing the buttons , and
. It is used mainly to protect against modifications in the Settings menu. The possible operations are
indicated in table 5.
Submenu item
Description
Optional Values
Default
value
Language
Select menu language
English / Chinese
English
User password*
Protects against settings modifications
enabled/disabled
disabled
Audio alarm
Enable/disable alarm sounds
enabled/disabled
enabled
Output voltage
Define local output voltage
200/208/220/230/240V
230V
Output frequency
Define local output frequency
autosensing/50/60Hz
UPS detects the frequency
when in ‘autosensing’
autosensing
Power strategy**
Define the running mode to normal,
ECO-mode or high efficiency and
converter mode
normal/high efficiency (ECO-
mode)/ converter
normal
DC start (Cold
start)
Start the UPS from the batteries (without
mains power)
enabled/disabled
enabled
Automatic battery
tests period
Define the frequency of the battery tests 0-31 days
7 days
Auto restart
After power outage, the loads restart
automatically when mains power is
recovered.
enabled/disabled
enabled
Automatic overload
restart
The UPS is automatically restarted if it
shutdown for overload.
enabled/disabled
enabled