PME120/RHD250 to 4000 (Contrac)
ELECTRICAL ROTARY ACTUATOR | OI/PME/RHD250/4000-EN REV. F
11
5
Installation
Safety instructions
DANGER
Danger to life due to falling or toppling loads.
Risk of death or serious injury due to the device falling down
or toppling over!
• Standing under suspended loads is prohibited.
• Do not detach the hoisting equipment until installation is
complete.
• Only use the dedicated load pick-up devices (eyebolts) for
suspending the components.
Please observe the following safety instructions
• Only qualified specialists may mount and adjust the control
actuator, and make the electrical connection.
• When working on the actuator or the electronics always
observe the locally valid accident prevention regulations and
the regulations concerning the construction of technical
installations.
• Switch off the supply voltage and take precautions to
prevent unintentional switch-on.
Mounting
Actuator check
Before you start to install the actuator make sure that the
delivery status corresponds to the ordered status and to the
intended use.
• Check the oil level when installing the device in positions
other than IMB 3.
• Once the actuator is installed, fasten the vent valve in the
uppermost oil hole.
• Prior to commissioning the device, make sure that the motor
and the connection chambers are free of dirt, humidity and
corrosion.
Installation instructions
• Make sure that no process forces are exerted on the final
control element.
• Do not lift the actuator by the motor or handwheel.
• The load pick-up device (eyebolt) attached to the actuator
may only be loaded in the vertical direction. Only use the load
pick-up device to lift / lower the actuator (without final
control element mounted).
• Make sure that the actuator is accessible from all sides so
that convenient handwheel operation, electrical connection,
or exchange of assemblies is possible.
• Select the installation location such to avoid direct exposure
to rain, snow and other environmental influences.
• The control actuators can withstand vibration loadings in
accordance with EN 60068-2-6, Table C.2 to 150 Hz and max.
2 g.
• The substructure should be designed to be level and torsion-
resistant.
• When mounting the actuator close to heat sources use an
insulating layer or shielding.
• Make sure that the maximum ambient temperature is not up-
scaled. If required, provide a sunshield to protect against
direct sunlight.
Fastening the actuator
1.
.Place the actuator on the fastening device in the correct
position. Pay attention to the rotating direction in
combination with the final control element.
2.
Fasten the actuator using four screws. Use the biggest
possible screw diameter and observe the tightening torque
(see table
Locking and fastening elements
on page 14).
Mounting position
The spur gearing of the actuator PME120 and RHD250 /
RHD500 / RHD800 / RHD1250 / RHD2500 / RHD4000 (Contrac)
are lubricated with oil. They contain the max. oil quantity when
leaving the manufacturer. Once the actuator is installed replace
the uppermost check plug by the separately supplied venting
plug.
1
Control screw
2
Vent valve
Figure 5: Permissible mounting positions
The mounting positions presented are permissible. To facilitate
mounting and maintenance, however, it is recommended that
you use position IMB 3 For each mounting position, you should
check the specified oil level before commissioning, ,
Filling
volumes
on page 40.